TH51, TH52, TH56
Hauser
5
Insulation resistance
Insulation resistance for MgO insulated thermocouples with ungrounded hot junction between terminals and
probe sheath, test voltage 500 Vdc.
• 1,000 M
Ω
at 77 °F (25 °C)
These values for insulation resistance apply also between each thermocouple wire at single and duplex
constructions with ungrounded hot junction.
Galvanic isolation
Galvanic isolation of Hauser iTEMP
®
transmitters (input/output)
In applications where fast response time is needed, grounded thermocouples are recommended. This
thermocouple design may cause a ground loop. This can be avoided by using iTEMP transmitters with high
galvanic isolation.
Wiring
Wiring diagrams
Type of sensor connection TH51
!
Note!
TH52 is available only with conductor external lead wires, DIN rail transmitters (TMT 121 PCP / TMT 122
HART
®
) are available, see 'Documentation'.
!
Note!
The blocks and transmitters are shown as they sit inside the heads in reference to the conduit opening.
Wire specifications
TH51
Thermocouple grade, TFE insulated 20AWG, 7 strands with wire termination
Transmitter type
Sensor
TMT 181 PCP
Û = 3.75 kV AC
TMT 182 HART
®
U = 2 kV AC
TMT 162 HART
®
Field transmitter
U = 2 kV AC
Head transmitter mounted
Terminal block mounted
T09-TH5156xx-04-xx-XX-ae-000
T09-TH5156xx-04-xx-XX-ae-001