WirelessHART Adapter SWA70
8 Configuration
Hauser
69
2. The primary variable is permanently linked to the scaled loop current. The scaling and unit can
be changed in the DTM navigation tree in the
Application Settings/4-20 mA
menu.
The following variables can be selected as the secondary, tertiary and quaternary variable:
–
Battery Voltage: current battery voltage
–
Battery Voltage With Load: battery voltage with a load
–
Battery Voltage Without Load During Battery Test
–
Consumed Energy: energy consumed
–
Estimated Lifetime: estimated lifetime in days
–
Normalized Consumed Energy: energy consumed under normalized conditions
–
RSL of Best Neighbor: signal strength of the "best" neighbor
–
RSL of Second Best Neighbor: signal strength of the "second-best" neighbor
–
Temperature: current temperature
–
Temperature Min: minimum temperature that has been measured by the WirelessHART
Adapter. The value can be reset.
–
Temperature Max: maximum temperature that has been measured by the WirelessHART
Adapter. The value can be reset.
The choice of unit matches the set variable.
Device variable mapping
parameters
8.3.5
4-20 mA (application setting)
When a HART device is connected to the WirelessHART Adapter, all the parameters are read via
the digital signal. However, it is also possible to connect a 4–20 mA device to the WirelessHART
Adapter. The WirelessHART Adapter then measures the loop current and can transmit it digitally.
It is possible to adjust the 4 to 20 mA signal in the adapter DTM and perform linearization if
necessary. In addition, you can enter limit values that specify the proportional value range and the
alarm signals. If the values entered are exceeded or undershot, the WirelessHART Adapter issues a
warning or an alarm, and an event notification where warranted. See the "Event notification
(application setting)" section on Page
1. Click
Application Settings/4-20 mA
in the DTM navigation tree
to display the appropriate
parameters.
–
You can enter text in the white fields. Press
Enter
to save your changes.
–
The gray fields are read-only.
–
An explanation of the individual parameters is provided in the "4-20 mA parameters" table
below. Mandatory fields are highlighted in bold.
Parameter
Meaning
Example
Default
Select Primary Variable
Primary variable
– The primary variable is permanently linked to
the loop current.
Scaled Loop Current Scaled Loop
Current
Primary Variable Unit
Unit of the primary variable
mbar
mA
Select Secondary Variable
Secondary variable
Temperature
Temperature
Secondary Variable Unit
Unit of the secondary variable
°C
°C
Select Tertiary Variable
Tertiary variable
RSL of Best
Neighbor
RSL of Best
Neighbor
Tertiary Variable Unit
Unit of the tertiary variable
dB
dB
Select Quaternary Variable Quaternary variable
Estimated Lifetime
Estimated Lifetime
Quaternary Variable Unit
Unit of the quaternary variable
d