![Endress+Hauser Soliswitch FTE20 Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/endress-hauser/soliswitch-fte20/soliswitch-fte20_operating-instructions-manual_2408469019.webp)
Soliswitch FTE20
Operation
Hauser
19
A0017366
å
13
Connect the cable to the terminals
5.3
Post-connection check
Device condition and specifications
Notes
Are cables or the device damaged?
Visual inspection
Electrical connection
Notes
Does the supply voltage match the specifications on the nameplate?
• 20 to 28 V DC
• 24 V AC
• 115 V AC
• 230 V AC
Are the mounted cables connected correctly and strain-relieved?
-
Are the cable glands securely tightened?
-
6
Operation
6.1
Adjusting the switching pressure
The switching pressure can be adjusted to 3 levels using an operating element accessible from
the top:
• Slight
³
80 g/l (4.99 lb/ft³)
• Medium
³
100 g/l (6.24 lb/ft³)
• High
³
120 g/l (7.49 lb/ft³)