Technical data
RN42
18
Hauser
Performance characteristics
Power supply
Supply voltage
24 to 230 V
AC/DC
(-20% / +10%, 0/50/60 Hz)
Power consumption
≤ 4.9 VA / 2.4 W (20 mA); ≤ 5 VA / 2.5 W (22 mA)
Power loss
≤ 2 W (20 mA); ≤ 2.1 W (22 mA)
Current consumption at 24 V
DC
≤ 0.1 A (20 mA); ≤ 0.1 A (22 mA)
Current consumption at 230 V
AC
≤ 0.02 A (20 mA); ≤ 0.02 A (22 mA)
1)
The data apply for the following operating scenario: input active / output active / output load 0 Ω. When
external voltages are connected to the output, the power loss in the device may increase. The power loss in
the device can be reduced by connecting an external output load.
Terminals
A flat-blade screwdriver is required to establish an electrical connection to screw or push-
in terminals.
0,5-0,6 Nm
5-7 lb In
7 mm (0,28")
AWG 24-14
0,2 -2,5 mm
5
²
AWG 24-14
0,2 - ,5 mm
5 2
²
10
(0,39")
mm
1.
2.
1.
1.
2.
3.
A0040201
8
Electrical connection using screw terminals (left) and push-in terminals (right)
Terminal design
Cable design
Cable cross-section
Screw terminals
Tightening torque: minimum 0.5
Nm/maximum 0.6 Nm
Rigid or flexible
(Stripping length = 7 mm (0.28 in)
0.2 to 2.5 mm² (24 to 14 AWG)
Flexible with wire end ferrules
(with or without plastic ferrule)
0.25 to 2.5 mm² (24 to 14 AWG)
Push-in spring terminals
Rigid or flexible
(Stripping length =
10 mm (0.39 in)
0.2 to 2.5 mm² (24 to 14 AWG)
Flexible with wire end ferrules
(with or without plastic ferrule)
0.25 to 2.5 mm² (24 to 14 AWG)
Cable specification
A shielded cable is recommended for HART communication. Observe grounding concept of
the plant.
12.5 Performance characteristics
Response time
Step response (10 to 90 %)
≤ 1 ms
Reference operating
conditions
• Calibration temperature: +25 °C ±3 K (77 °F ±5.4 °F)
• Supply voltage: 24 V
DC
/ 230 V
AC
• Output load: 225 Ω
• External output voltage (passive output): 20 V
DC
• Warm-up: > 1 h