Prosonic M FMU40

HART

Ultrasonic measuring technology

BA01961F/00/EN/01.22-00

71566680

2022-04-04

Содержание Prosonic M FMU40

Страница 1: ...Products Solutions Services Operating Instructions Prosonic M FMU40 HART Ultrasonic measuring technology BA01961F 00 EN 01 22 00 71566680 2022 04 04...

Страница 2: ...Prosonic M FMU40 HART 2 Endress Hauser Order code Ext ord cd Ser no www endress com deviceviewer Endress Hauser Operations App XXXXXXXXXXXX XXXXX XXXXXX XXX XXXX XX Serial number 1 3 2 A0023555...

Страница 3: ...function of the operating menu 20 7 3 Access to the operating menu via the local display 21 7 4 Access to the operating menu via the operating tool 23 7 5 Locking or enabling parameter configuration...

Страница 4: ...lt in minor or medium injury NOTICE This symbol contains information on procedures and other facts which do not result in personal injury 1 2 2 Electrical symbols Ground connection Grounded clamp whic...

Страница 5: ...tructions document is located under the housing cover of the device The most important functions of the menu are summarized in this document Description of Device Parameters BA Reference manual for pa...

Страница 6: ...ations 2 4 Operational safety Risk of injury Operate the device only if it is in proper technical condition free from errors and faults The operator is responsible for ensuring failure free operation...

Страница 7: ...e is installed and used as described in the Operating Instructions Provide additional protection for the device and data transfer to from the device IT security measures defined in the plant owner ope...

Страница 8: ...If one of these conditions is not satisfied contact your Sales Center 4 2 Product identification The device can be identified in the following ways Nameplate specifications Extended order code with br...

Страница 9: ...of the device to ensure that the device does not tilt or slip Follow the safety instructions and transport conditions for devices weighing more than 18 kg 39 6 lb IEC 61010 5 Mounting 5 1 Mounting re...

Страница 10: ...angle is defined as the beam angle At the energy density of the ultrasonic wave reaches half the value of the maximum energy density Ultrasonic waves are also emitted outside the signal beam and can...

Страница 11: ...he sensor membrane so that it is parallel to the surface of the water Observe the installation clearance of the flume or weir Enter the flow level Q h curve linearization curve via the FieldCare opera...

Страница 12: ...HART 12 Endress Hauser BD E 2 H max 2 Hmax a H max F 3 Hmax A0038223 8 Triangular weir example BD Blocking distance of the sensor E Empty calibration enter during commissioning F Full calibration Hma...

Страница 13: ...ng examples A With counter nut B With welding boss C With mounting bracket D With screw in flange 5 1 6 Mounting the device NOTICE The device can be damaged Tighten the device at the threaded boss onl...

Страница 14: ...Blocking distance BD 0 25 m 0 8 ft Maximum range for liquids 5 m 16 ft Maximum range for bulk solids 2 m 6 6 ft 5 2 2 Blocking distance NOTICE If the blocking distance is undershot this may cause a de...

Страница 15: ...zle diameter L Nozzle length Conditions Smooth interior surfaces in pipe nozzle Remove any edges or welded joints and burr on the inside of the tank side nozzle end To minimize disturbing factors nozz...

Страница 16: ...unting check Is the device free from damage visual inspection Does the measuring device comply with the measuring point specifications After aligning the housing is the process seal on the nozzle or f...

Страница 17: ...is fitted Remove the cable from the display 4 5 6 A0038243 A0038252 A0038253 Pull out the terminal module slightly using the pull loop Avoid moisture in the housing provide a loop to allow moisture to...

Страница 18: ...hield to the ground terminal in the connection compartment Tighten the cable gland 6 Close the housing 7 Switch on the power supply 6 3 Terminal assignment 2 4 3 1 2 3 4 L L I I 1 A0019269 14 Terminal...

Страница 19: ...age 14 to 30 V Current consumption 20 mA terminal voltage 8 to 30 V Ex d Current consumption 4 mA terminal voltage 14 to 30 V Current consumption 20 mA terminal voltage 11 to 30 V Fixed current termin...

Страница 20: ...upply voltage match the specifications on the nameplate No reverse polarity terminal assignment correct Do the cables used comply with the requirements Are the cable glands tightened correctly Is the...

Страница 21: ...display 7 3 1 Display 4 1 6 3 5 2 A0047443 16 Measured value display 1 Label e g measured value 2 Symbol 3 Value and unit e g 43 2 4 Position in menu e g 000 5 Bar graph 6 Position in menu The bar gra...

Страница 22: ...1 Operating keys Navigate up in the picklist Edit the numerical values within a function Navigate down in the picklist Edit the numerical values within a function Simultaneously Navigate to the left...

Страница 23: ...next character and continue editing until you have entered the entire value 3 If a symbol appears at the cursor press to accept the value entered Editing mode inactive 4 If a symbol appears at the cur...

Страница 24: ...Hardware locking only possible via the display press again simultaneously Hardware unlocking via communication is not possible 8 System integration 8 1 4 to 20 mA output with HART protocol 8 1 1 Opera...

Страница 25: ...View in the FieldCare operating program Select the function groups and functions of the device via the navigation bar Enter parameters in the input window Click the parameter names and call up exact...

Страница 26: ...r and labeling correct visual inspection Is the measuring device adequately protected against precipitation and direct sunlight 9 1 2 Post connection check Are the device or cables undamaged visual in...

Страница 27: ...with the local display 9 4 Configuring the measuring device 9 4 1 Basic setup F E BD SD A0038238 23 Parameters for the correct operation of the device BD Blocking distance SD Safety distance E Empty c...

Страница 28: ...e function A Dome ceiling B Horizontal cyl C Bypass or stilling well ultrasound guide pipe D No ceiling e g dumps open levels basins flume E Sphere F Flat ceiling Medium properties function 003 Select...

Страница 29: ...le measured value accurate measurement slow response time Turb surface For storage and buffer tanks with turbulent surfaces due to free filling mixing nozzles or small bottom agitators Emphasis on fil...

Страница 30: ...operation of the device D Distance sensor membrane product E Empty calibration zero point F Full calibration measuring span L Level BD Blocking distance SD Safety distance Empty calibration function 0...

Страница 31: ...el L Check whether the values displayed match the actual distance level Check distance function 051 Start the mapping process A B A0038449 27 Example of mapping A Distance too small B Distance Ok Sele...

Страница 32: ...vel The following situations can occur Distance and level correct Basic setup completed Distance and level incorrect perform another mapping in the Check distance 051 function Distance is correct but...

Страница 33: ...ally no interference echoes in front of the actual level signal Interference echoes must be below the mapping curve 1 2 3 4 5 6 7 A0038455 28 Envelope curve 1 Full calibration 2 Quality of the evaluat...

Страница 34: ...3 Exiting the navigation 1 Press repeatedly Cyclically run through the various modes of the envelope curve navigation 2 Press simultaneously The set increases and shifts are retained 3 Activate the R...

Страница 35: ...oad error Check the connection Start downloading again A111 A113 A114 A115 A121 A125 A155 A164 A171 Electronics defective Perform a reset Check system for EMC If the alarm persists after a reset repla...

Страница 36: ...imulation on Switch off the simulation mode Output 06 function group Simulation 065 function W681 Current out of range Perform the basic setup Check linearization W691 Noise filling 10 5 Application e...

Страница 37: ...easured value when filling or emptying Example 100 0 t A B A0038460 A Expected result B Error occurred 1 Perform mapping 2 Clean sensor 3 Select a better installation position 4 If very large interfer...

Страница 38: ...tor 3 Increase the output damping 058 4 Select another installation position and or a larger sensor Error During filling or emptying the measured value drops Example 100 0 A B t A0038463 A Expected re...

Страница 39: ...nearization switches to linear table values are retained Switch the table in the Linearization 04 function group Linearization 041 function back on Navigation Diagnostics 0A function group Reset 0A3 f...

Страница 40: ...006 Valid from documentation version BA237F 00 en 07 06 Detection window added Version 07 06 Software changes Detection window function added Compatible with ToF tool from version 4 50 HART Communicat...

Страница 41: ...ronics module has been replaced the parameters can be downloaded to the device again via the communication interface For this the data must have been uploaded to the PC beforehand using FieldCare You...

Страница 42: ...2 250 9 84 G 16 0 6 3 0 12 A0019346 30 Dimensions of mounting bracket Unit of measurement mm in G Process connection Order number G 1 71452324 Material 316L 1 4404 Weight 2 8 kg 6 17 lb Also suitable...

Страница 43: ...94 60 2 36 4 0 16 6 5 0 3 109 4 29 75 2 95 A0037799 32 Dimensions Unit of measurement mm in Weight 4 2 kg 9 26 lb Material 316L 1 4404 Order number 71452327 13 1 4 Frame 1400 mm 55 1 in 3 2 0 13 20 0...

Страница 44: ...er number 71452326 13 1 5 Wall bracket for cantilever with pivot 110 4 3 25 1 0 4 0 16 6 5 0 3 150 5 9 33 7 1 3 3 2 0 1 110 4 3 13 0 5 150 5 9 180 7 1 213 8 4 88 3 5 A0019350 34 Dimensions of the wall...

Страница 45: ...08 6 5 0 3 15 0 6 100 3 9 25 1 0 35 1 4 100 3 9 75 2 9 250 9 84 20 0 8 75 2 9 2 0 08 A0037802 35 Dimensions Unit of measurement mm in Weight 3 01 kg 6 84 lb Material 316L 1 4404 Order number 71452318...

Страница 46: ...s Unit of measurement mm in Weight 5 2 kg 11 47 lb Material 316L 1 4404 Order number 71452319 50 mm 2 17 in openings for all G 1 MNPT 1 connections on front 22 mm 0 87 in opening can be used for an ad...

Страница 47: ...IP 65 3 Cable 4 Pipe Technical data Cable length 20 m 66 ft fixed length with cast on connectors Temperature range T6 40 to 60 C 40 to 140 F Temperature range T5 40 to 75 C 40 to 167 F Degree of prot...

Страница 48: ...CDI interface Common Data Interface of Endress Hauser devices to the USB port of a computer Order number 51516983 Accessory ToF Adapter FXA291 Additional information Technical Information TI00405C 13...

Страница 49: ...odbus FXA30B or HART FXA30B With its robust design and ability to run for years on the battery it is ideal for remote monitoring in isolated locations Version with LTE USA Canada and Mexico only or 3G...

Страница 50: ...nge for liquids 5 m 16 ft Maximum range for bulk solids 2 m 6 6 ft 14 1 3 Operating frequency sound pressure level Operating frequency approx 70 kHz Maximum sound pressure level directly in front of t...

Страница 51: ...tion 11 mA terminal voltage 10 to 30 V Fixed current for Multidrop mode Standard Current consumption 4 mA start up current 11 mA terminal voltage 14 to 36 V Ex ia Current consumption 4 mA start up cur...

Страница 52: ...hase The vapor pressure of the medium at 20 C 68 F is an indicator of the accuracy of the ultrasonic level measurement Accuracy Very good accuracy vapor pressure at 20 C 68 F less than 50 mbar 1 psi T...

Страница 53: ...patibility Electromagnetic compatibility in accordance with all of the relevant requirements outlined in EN 61326 series and NAMUR Recommendation EMC NE 21 More information is provided in the Declarat...

Страница 54: ...n 04 Level ullage 040 Linearization 041 Customer unit 042 Table no 043 Input level 044 Input volume 045 Max scale 046 Diameter vessel 047 Extended calibration 05 Selection 050 Check distance 051 Range...

Страница 55: ...ter 096 Display test 097 Diagnostic 0A Present error 0A0 Previous error 0A1 Clear last error 0A2 Reset 0A3 Unlock parameter 0A4 Measured dist 0A5 Measured level 0A6 Detection window 0A7 Application pa...

Страница 56: ...eter configuration 24 Envelope curve Checking the measuring signal 32 Envelope curve display 33 Error codes 35 F Fieldcare Establishing the connection 27 FieldCare 24 Firmware history 40 Flow measurem...

Страница 57: ...ty instructions 6 Safety symbols 4 Screw in flange 42 Software locking 24 Start mapping 053 function 32 Storage transport 9 Structure of the operating menu 20 Supplementary documentation Additional do...