Electrical connection
7.1
Connection conditions
7.1.1
Required tools
• For cable entries: Use corresponding tools
• Wire stripper
• When using stranded cables: Crimping tool for ferrule
• Flat blade screwdriver≤3 mm (0.12 in)
7.1.2
Requirements for connecting cable
The connecting cables provided by the customer must fulfill the following requirements.
Electrical safety
In accordance with applicable federal/national regulations.
Permitted temperature range
• –40 °C (–40 °F) to ≥ +80 °C (+176 °F)
• Minimum requirement: cable temperature range ≥ ambient tempe20 K
Power supply cable
Standard installation cable is sufficient.
Signal cable
Current output
For 4-20 mA HART: Shielded cable recommended. Observe grounding concept of the plant.
Pulse/frequency/switch output, status input
Standard installation cable is sufficient.
Cable diameter
• Included cable glands: M20 × 1.5 with cable 6 to 12 mm (0.24 to 0.47 in)
• Wire cross-sections 0.5 to 1.5 mm
2
(21 to 16 AWG)