SIMULATION SYSTEM
Proline t-mass 65 MODBUS RS485
52
Hauser
18
SIMULATION SYSTEM
Function description, SIMULATION SYSTEM group
SIMULATION FAILSAFE
MODE
Description
Use this function to set all inputs, outputs and the totalizer to their error
response modes, in order to check whether they respond correctly. During this
time, the message #691 "SIMULATION FAILSAFE" appears on the display.
Options
0 = OFF
1 = ON
Factory setting
OFF
MODBUS register:
Data type:
Access:
6812
Integer
read/write
SIMULATION MEASURAND
Description
Use this function to set all the inputs, outputs and the totalizer to their flow
response modes, in order to check whether they respond correctly. During this
time, the message #692 "SIMULATION MEASURAND" appears on the display.
!
Note!
• The measuring device can only be used for measuring to a certain extent
while the simulation is in progress.
• The setting is not saved if the power supply fails.
Options
0 = OFF
1 = MASS FLOW
2 = CORRECTED VOLUME FLOW
3 = TEMPERATURE
4 = HEAT FLOW
Factory setting
OFF
MODBUS register:
Data type:
Access:
6813
Integer
read/write
VALUE SIMULATION
MEASURAND
Prerequisite
Function is
only
available if the SIMULATION MEASURAND function
52) is active.
Description
Use this function to specify an arbitrary value (e.g. 12 kg/s) to check the
assigned functions in the device itself and downstream signal circuits.
The unit depends on the option selected in the SIMULATION MEASURAND
function and is taken from the SYSTEM UNITS group (
8).
!
Note!
The setting is not saved if the power supply fails.
User input
5-digit floating-point number
Factory setting
(country dependent
55)
• 0 kg/h; 0 lb/h (MASS FLOW)
• 0 Nm³/h; 0 Sm³/h (CORRECTED VOLUME FLOW)
• 0 MWh; 0 kBtu (HEAT FLOW)
• 0 °C; +32 °F (TEMPERATURE)
MODBUS register:
Data type:
Access:
6814
Float
read/write