Proline t-mass 65 MODBUS RS485
COMMUNICATION
Hauser
33
11
COMMUNICATION
Function description, COMMUNICATION group
TAG NAME
Description
Use this function to enter a tag name for the device. You can edit and read
this tag name at the local display or via the MODBUS communication..
User input
Max. 16-character text, permitted characters are: A-Z, 0-9, +,–, punctuation
marks
Factory setting
"– – – – – – – – – – – – – – – –" (no text)
MODBUS register:
Data type:
Access:
4901
String (16)
read/write
FIELDBUS ADDRESS
Description
For entering the device address.
User input
1 to 247
Factory setting
247
MODBUS register:
Data type:
Access:
4910
Integer
read/write
BAUDRATE
Description
Use this function for selecting the baud rate.
Options
0 = 1200 BAUD
1 = 2400 BAUD
2 = 4800 BAUD
3 = 9600 BAUD
4 = 19200 BAUD
5 = 38400 BAUD
6 = 57600 BAUD
7 = 115200 BAUD
Factory setting
19200 BAUD
MODBUS register:
Data type:
Access:
4912
Integer
read/write
TRANSMISSION MODE
Description
Use this function for selecting the data transfer mode.
Options
0 = RTU
Transmission of data in binary form.
Error protection via CRC16.
1 = ASCII
Transmission of data in the form of readable ASCII characters.
Error protection via LRC.
Factory setting
RTU
MODBUS register:
Data type:
Access:
4913
Integer
read/write
PARITY
Description
Use this function for selecting whether no parity bit or an even or odd parity
bit should be transmitted.
Options
0 = EVEN
1 = ODD
2 = NONE/STOP BITS 2
3 = NONE/STOP BITS 1
Factory setting
EVEN
MODBUS register:
Data type:
Access:
4914
Integer
read/write