Proline t-mass 65 MODBUS RS485
USER INTERFACE
Hauser
27
BACKLIGHT
Description
For adjusting the background lighting to suit local operating conditions.
Entering the value "0" means that the backlight is "switched off". The display
then no longer emits any light, i.e. the display texts can no longer be read in the
dark.
User input
0 to 100%
Factory setting
50%
MODBUS register:
Data type:
Access:
2566
Float
read/write
TEST DISPLAY
Description
Use this function to test the operability of the local display and its pixels.
Test sequence:
1.
Start the test by selecting ON.
2.
All pixels of the main line and additional line are darkened for minimum
0.75 seconds.
3.
The main line and additional line show an "8" in each field for minimum
0.75 seconds.
4.
The main line and additional line show a "0" in each field for minimum
0.75 seconds.
5.
The main line and additional line show nothing (blank display) for
minimum 0.75 seconds.
6.
When the test is completed, the local display returns to its initial state and
displays the option OFF.
Options
0 = OFF
1 = ON
Factory setting
OFF
MODBUS register:
Data type:
Access:
2513
Integer
read/write
Function description, USER INTERFACE group