Proline Prosonic Flow 93
Installation
Hauser
23
7.
Coat the contact surfaces of the sensors with an even layer of coupling fluid approx. 1 mm
(0.04") thick, going from the groove through the center to the opposite edge.
A0011373
Fig. 15: Coating the contact surfaces of the sensor with coupling fluid
8.
Insert the sensor into the sensor holder.
9.
Fit the sensor cover on the sensor holder and turn until:
– The sensor cover engages with a click
– The arrows (
Å
/
Æ
"close") are pointing towards one another.
10. Screw the connecting cable into the individual sensor.
A0001115
Fig. 16: Mounting the sensor and connecting the connecting cable
This completes the mounting process. The sensors can now be connected to the transmitter via
the connecting cables