Commissioning
Proline Promass Q 500 PROFIBUS PA
108
Hauser
Parameter
Prerequisite
Description
Selection / User
entry
Factory setting
Fail safe type
–
Select the failure mode.
• Fail safe value
• Fallback value
• Off
Off
Fail safe value
In
Fail safe type
parameter,
the
Fail safe value
option is
selected.
Specify the values to be output
when an error occurs.
Signed floating-point
number
0
*
Visibility depends on order options or device settings
10.6.6 Displaying the I/O configuration
The
I/O configuration
submenu guides the user systematically through all the parameters
in which the configuration of the I/O modules is displayed.
Navigation
"Setup" menu → I/O configuration
‣
I/O configuration
I/O module 1 to n terminal numbers
I/O module 1 to n information
I/O module 1 to n type
Apply I/O configuration
Conversion code
Parameter overview with brief description
Parameter
Description
User interface / Selection /
User entry
Factory setting
I/O module 1 to n terminal numbers Shows the terminal numbers used by the I/O
module.
• Not used
• 26-27 (I/O 1)
• 24-25 (I/O 2)
–
I/O module 1 to n information
Shows information of the plugged I/O
module.
• Not plugged
• Invalid
• Not configurable
• Configurable
• Fieldbus
–
I/O module 1 to n type
Shows the I/O module type.
• Off
• Current output
• Current input
• Status input
• Pulse/frequency/switch
output
Off
Apply I/O configuration
Apply parameterization of the freely
configurable I/O module.
• No
• Yes
No
Conversion code
Enter the code in order to change the I/O
configuration.
Positive integer
0
*
Visibility depends on order options or device settings