background image

Proline Promass I 100

80

Hauser

• NAMUR NE 53

Software of field devices and signal-processing devices with digital electronics

• NAMUR NE 80

The application of the pressure equipment directive to process control devices

• NAMUR NE 105

Specifications for integrating fieldbus devices in engineering tools for field devices

• NAMUR NE 107

Self-monitoring and diagnosis of field devices

• NAMUR NE 131

Requirements for field devices for standard applications

• NAMUR NE 132

Coriolis mass meter

Ordering information

Detailed ordering information is available from the following sources:

• In the Product Configurator on the Hauser website: 

www.endress.com

 → Select country →

Instruments → Select device → Product page function: Configure this product

• From your Hauser Sales Center: 

www.endress.com/worldwide

Product Configurator - the tool for individual product configuration

• Up-to-the-minute configuration data

• Depending on the device: Direct input of measuring point-specific information such as

measuring range or operating language

• Automatic verification of exclusion criteria

• Automatic creation of the order code and its breakdown in PDF or Excel output format

• Ability to order directly in the Hauser Online Shop

Application packages

Many different application packages are available to enhance the functionality of the device. Such

packages might be needed to address safety aspects or specific application requirements.
The application packages can be ordered from Hauser either directly with the device or

subsequently. Detailed information on the order code in question is available from your local Endress

+Hauser sales center or on the product page of the Hauser website: 

www.endress.com

.

Heartbeat Technology

Package

Description

Heartbeat Verification

+Monitoring

Heartbeat Monitoring:

Continuously supplies monitoring data, which are characteristic of the measuring

principle, for an external condition monitoring system. This makes it possible to:

• Draw conclusions - using these data and other information - about the impact

the measuring application has on the measuring performance over time.

• Schedule servicing in time.

• Monitor the product quality, e.g. gas pockets.

Heartbeat Verification:

Makes it possible to check the device functionality on demand when the device is

installed, without having to interrupt the process.

• Access via onsite operation or other operating interfaces, such as FieldCare for

instance.

• Documentation of device functionality within the framework of manufacturer

specifications, for proof testing for instance.

• End-to-end, traceable documentation of the verification results, including report.

• Makes it possible to extend calibration intervals in accordance with operator's

risk assessment.

Содержание Proline Promass I 100

Страница 1: ...compact transmitter housing High ingress protection IP69K Local display available Your benefits Energy saving minimum pressure loss thanks to full bore design Fewer process measuring points multivari...

Страница 2: ...Safety Barrier Promass 100 42 Environment 42 Ambient temperature range 42 Storage temperature 44 Climate class 44 Degree of protection 44 Shock resistance 44 Vibration resistance 44 Interior cleaning...

Страница 3: ...Proline Promass I 100 Endress Hauser 3 Registered trademarks 84...

Страница 4: ...hing any other connections Equipotential connection A connection that has to be connected to the plant grounding system This may be a potential equalization line or a star grounding system depending o...

Страница 5: ...ow causes deceleration of the oscillation at the inlet of the tubes 2 and acceleration at the outlet 3 1 2 3 A0016772 The phase difference A B increases with increasing mass flow Electrodynamic sensor...

Страница 6: ...b browser e g Microsoft Internet Explorer Also for device version with EtherNet IP output Via Web browser e g Microsoft Internet Explorer Via Add on Profile Level 3 for automation system from Rockwell...

Страница 7: ...ne 1 Div 1 Safety IT security We only provide a warranty if the device is installed and used as described in the Operating Instructions The device is equipped with security mechanisms to protect it ag...

Страница 8: ...The full scale values depend on the density of the gas and can be calculated with the formula below max G max F G x max G Maximum full scale value for gas kg h max F Maximum full scale value for liqu...

Страница 9: ...Damping Adjustable 0 07 to 999 s Assignable measured variables Mass flow Volume flow Corrected volume flow Density Reference density Temperature The range of options increases if the measuring device...

Страница 10: ...ction monitoring Status Partially filled pipe detection Low flow cut off The range of options increases if the measuring device has one or more application packages PROFIBUS DP Signal encoding NRZ cod...

Страница 11: ...ncy output Failure mode Choose from Actual value Defined value 0 to 12500 Hz 0 Hz Switch output Failure mode Choose from Current status Open Closed PROFIBUS DP Status and alarm messages Diagnostics in...

Страница 12: ...vailable EtherNet IP connection established Ex connection data These values only apply for the following device version Order code for Output option M Modbus RS485 for use in intrinsically safe areas...

Страница 13: ...C US IS Cl I II III Div 1 Ui 16 24 V Ii 623 mA Pi 2 45 W Li 0 H Ci 6 nF For an overview and for information on the interdependencies between the gas group sensor nominal diameter see the Safety Instr...

Страница 14: ...red variables are available with the Heartbeat Technology application package Sensor integrity Carrier pipe temperature Frequency fluctuation 1 Oscillation amplitude 1 Tube damping fluctuation 1 Excit...

Страница 15: ...assignment Pressure Temperature Reference density Digital output 1 to 3 fixed assignment Digital output 1 switch positive zero return on off Digital output 2 perform zero point adjustment Digital out...

Страница 16: ...type 0x2B Manufacturer ID 0x49E Device type ID 0x104A Baud rates Automatic Mbit with half duplex and full duplex detection Polarity Auto polarity for automatic correction of crossed TxD and RxD pairs...

Страница 17: ...tion 0xC7 T O configuration 0x64 44 Input Assembly Current device diagnostics Mass flow Volume flow Corrected volume flow Density Reference density Temperature Totalizer 1 Totalizer 2 Totalizer 3 Conf...

Страница 18: ...tion Activation of reference density compensation Activation of temperature compensation Reset totalizers 1 3 External pressure value Pressure unit External reference density Reference density unit Ex...

Страница 19: ...ug 1 Connection version 4 20 mA HART pulse frequency switch output 1 1 Signal transmission pulse frequency switch output 1 2 Signal transmission 4 20 mA HART 1 3 Supply voltage 2 Connection version Mo...

Страница 20: ...G Option U plug M12x1 thread M20 Options A B C Device plug Device plug Option Q 2 x plug M12x1 Order code for Housing Option A compact coated aluminum Option B compact hygienic stainless Option C ult...

Страница 21: ...ad NPT Options A B Device plug Terminals Option L plug M12x1 thread NPT Option N plug M12x1 coupling M20 Option P plug M12x1 thread G Option U plug M12x1 thread M20 Options A B C Device plug Device pl...

Страница 22: ...12x1 thread NPT Option N plug M12x1 coupling M20 Option P plug M12x1 thread G Option U plug M12x1 thread M20 Options A B C Device plug Device plug Option Q 2 x plug M12x1 Order code for Housing Option...

Страница 23: ...1 Option C thread G Option D thread NPT A B C Device plug Option I plug M12x1 Order code for Housing Option A compact coated aluminum Option B compact hygienic stainless Option C ultra compact hygieni...

Страница 24: ...M12x1 thread NPT Option N plug M12x1 coupling M20 Option P plug M12x1 thread G Option U plug M12x1 thread M20 Options A B C Device plug Device plug Option Q 2 x plug M12x1 Order code for Housing Optio...

Страница 25: ...4 20 mA HART pulse frequency switch output 19 PROFIBUS DP 21 Modbus RS485 22 EtherNet IP 24 Supply voltage For all connection versions except MODBUS RS485 intrinsically safe device side Device plug MO...

Страница 26: ...ce plug for signal transmission device side 3 2 4 1 5 A0016811 Pin Assignment Coding Plug socket 1 B Socket 2 A PROFIBUS DP 3 4 B PROFIBUS DP 5 Grounding shielding Recommended plug Binder series 763 p...

Страница 27: ...99 3729 810 04 Phoenix part no 1543223 SACC M12MSD 4Q When using the device in a hazardous location Use a suitably certified plug Supply voltage Transmitter For device version with all communication...

Страница 28: ...M Modbus RS485 for use in intrinsically safe areas 230 mA 10 A 0 8 ms Power supply failure Totalizers stop at the last value measured Depending on the device version the configuration is retained in t...

Страница 29: ...74 4 Resistor for HART communication 250 observe maximum load 9 5 Analog display unit observe maximum load 9 6 Transmitter Pulse frequency output 1 _ 12345 2 3 A0016801 9 Connection example for pulse...

Страница 30: ...specifications 33 3 Distribution box 4 Transmitter If baud rates 1 5 MBaud an EMC cable entry must be used and the cable shield must continue as far as the terminal wherever possible Modbus RS485 2 1...

Страница 31: ...able shield observe cable specifications 33 3 Safety Barrier Promass 100 4 Observe cable specifications 33 5 Non hazardous area 6 Non hazardous area and Zone 2 Div 2 7 Intrinsically safe area 8 Transm...

Страница 32: ...current input e g PLC Prerequisite automation system with HART version 6 HART commands 113 and 114 can be processed 2 Cable shield observe cable specifications 33 3 Resistor for HART communication 25...

Страница 33: ...34 mm2 22 AWG Cable type Twisted pairs Loop resistance 110 km Signal damping Max 9 dB over the entire length of the cable cross section Shielding Copper braided shielding or braided shielding with fo...

Страница 34: ...AWG m ft 0 5 20 70 230 0 75 18 100 328 1 0 17 100 328 1 5 16 200 656 2 5 14 300 984 Performance characteristics Reference operating conditions Error limits based on ISO 11631 Water with 15 to 45 C 59...

Страница 35: ...0 40 20 4 15 6500 650 325 130 65 13 15 FB 18000 1800 900 360 180 36 25 18000 1800 900 360 180 36 25 FB 45000 4500 2250 900 450 90 40 45000 4500 2250 900 450 90 40 FB 70000 7000 3500 1400 700 140 50 70...

Страница 36: ...ow gases 0 25 o r Design fundamentals 37 Density liquids 0 00025 g cm3 Temperature 0 25 C 0 0025 T C 0 45 F 0 0015 T 32 F Response time The response time depends on the configuration damping Influence...

Страница 37: ...re The table below shows the effect on accuracy of mass flow due to a difference between calibration pressure and process pressure o r of reading DN o r bar o r psi mm in 8 no influence no influence 1...

Страница 38: ...eRepeat 100 A0021336 ZeroPoint MeasValue 100 A0021337 Example for max measured error E Q 0 5 10 15 20 25 30 35 40 45 50 60 65 55 0 0 5 1 0 1 5 2 0 2 5 70 75 80 85 90 95 100 A0016709 E Error Maximum me...

Страница 39: ...the nominal diameter prevent the sensor running empty while measurement is in progress 1 2 3 4 5 A0015596 17 Installation in a down pipe e g for batching applications 1 Supply tank 2 Sensor 3 Orifice...

Страница 40: ...mitter this orientation is recommended Inlet and outlet runs No special precautions need to be taken for fittings which create turbulence such as valves elbows or T pieces as long as no cavitation occ...

Страница 41: ...7 C mm 40 40 44 5 44 5 60 60 80 80 90 90 US units DN in FB 1 1 FB 1 1 FB 2 2 FB 3 A in 14 69 16 1 21 22 21 22 26 3 26 3 30 71 30 71 45 35 45 35 B in 0 79 0 79 1 18 1 18 1 1 1 1 1 38 1 38 2 24 2 24 C i...

Страница 42: ...fety Barrier Promass 100 40 to 60 C 40 to 140 F If operating outdoors Avoid direct sunlight particularly in warm climatic regions Weather protection covers can be ordered from Endress Hauser see Acces...

Страница 43: ...a maximum medium temperature Tm 392 F Tm 392 F Ex nA CCSAUS NI SI units Order code for Housing Ta C T6 85 C T5 100 C T4 135 C T3 200 C T2 300 C T1 450 C Option A Compact coated alu Option B Compact hy...

Страница 44: ...is immediately greater than or equal to the measured maximum ambient temperature Tma that is present Ta 50 C The row showing the maximum medium temperature is determined 3 Select the maximum medium te...

Страница 45: ...ue as far as the terminal wherever possible For details refer to the Declaration of Conformity Process Medium temperature range Sensor 50 to 150 C 58 to 302 F Seals No internal seals Density 0 to 5000...

Страница 46: ...200 300 F 350 250 200 150 100 50 0 50 C 200 150 100 50 0 50 400 A0020923 EN 22 With flange material 1 4301 304 wetted parts titanium Flange connection according to JIS B2220 0 10 20 30 40 50 70 60 bar...

Страница 47: ...t when selecting seals and counterparts as these components can limit the pressure and temperature range Aseptic threaded adapter as per DIN 11864 1 Form A 0 10 20 30 40 DN8 40 DN40FB DN50 DN50FB DN80...

Страница 48: ...50 FB 2 FB 40 580 460 6670 80 3 40 580 460 6670 FB Full bore If there is a risk of measuring tube failure due to process characteristics e g with corrosive process fluids we recommend the use of senso...

Страница 49: ...pressure loss use the Applicator sizing tool 82 System pressure It is important that cavitation does not occur or that gases entrained in the liquids do not outgas This is prevented by means of a suff...

Страница 50: ...on thickness with ambient temperature of Ta 40 C 104 F T60 140 Insulation thickness with ambient temperature of Ta 60 C 140 F NOTICE The insulation can also be thicker than the recommended insulation...

Страница 51: ...roline Promass I 100 Endress Hauser 51 Vibrations The high oscillation frequency of the measuring tubes ensures that the correct operation of the measuring system is not influenced by plant vibrations...

Страница 52: ...35 62 3 50 136 147 5 93 5 54 256 6 340 8 35 62 3 50 FB 136 147 5 93 5 54 256 6 366 2 54 8 3 80 136 147 5 93 5 54 256 6 366 2 54 8 3 FB Full bore 1 If using an extension neck for the extended temperat...

Страница 53: ...ensions SI units DN mm A mm B mm C mm D mm E 2 mm F 1 2 mm G mm L mm 8 133 5 136 8 78 58 8 202 2 264 4 8 55 3 15 133 5 136 8 78 58 8 202 2 264 4 11 38 3 15 FB 133 5 136 8 78 58 8 202 2 264 4 17 07 3 2...

Страница 54: ...ature range order code for Sensor option option CG values 2 76 in 2 If using a display order code for Display Operation option B values 0 55 in 3 dependent on respective process connection Order code...

Страница 55: ...FB 4 39 4 87 2 67 2 2 7 96 10 41 0 672 3 1 4 39 4 87 2 67 2 2 8 34 10 79 0 672 3 1 FB 4 39 4 87 2 67 2 2 8 34 11 32 1 038 3 1 4 39 4 87 2 67 2 2 8 91 11 89 1 038 3 1 FB 4 39 4 87 2 67 2 2 8 91 12 42...

Страница 56: ...wetted parts titanium order code for Process connection option D3W Surface roughness flange EN 1092 1 Form B2 DIN 2526 Form E Ra 0 8 to 3 2 m DN mm A mm B mm C mm D mm E mm L mm 50 180 135 4 22 34 54...

Страница 57: ...78 25 FB 110 79 4 4 15 7 22 25 60 700 40 125 98 4 4 15 7 26 40 90 708 40 FB 125 98 4 4 15 7 24 35 62 819 50 150 120 7 4 19 1 28 52 60 827 50 FB 150 120 7 4 19 1 40 54 8 1210 80 190 152 4 4 19 1 37 78...

Страница 58: ...parts titanium order code for Process connection option ACW Surface roughness flange Ra 3 2 to 6 3 m DN mm A mm B mm C mm D mm E mm L mm 8 1 95 66 7 4 15 7 20 13 80 402 15 95 66 7 4 15 7 20 13 80 438...

Страница 59: ...125 90 4 19 23 25 00 578 25 FB 125 90 4 19 22 25 60 700 40 140 105 4 19 26 40 00 708 40 FB 140 105 4 19 24 35 62 819 50 155 120 8 19 28 50 00 827 50 FB 155 120 8 19 42 54 8 1210 80 200 160 8 23 36 80...

Страница 60: ...130 4 25 36 35 00 708 40 FB 175 130 4 25 37 35 62 825 50 185 145 8 23 40 48 00 832 50 FB 185 145 8 23 47 54 8 1210 80 230 185 8 25 55 73 1226 FB Full bore 1 DN 8 with DN 15 flanges as standard Tri Cl...

Страница 61: ...5 25 0 16 0 462 15 FB 25 0 16 0 602 3A version available order code for Additional approval option LP in combination with Ra 0 8 m Ra 0 4 m order code for Measuring tube material option CB CD FB Full...

Страница 62: ...itional approval option LP in combination with Ra 0 8 m Ra 0 4 m order code for Measuring tube material option CB CD FB Full bore Additional information on Eccentric clamps 40 Threaded hygienic connec...

Страница 63: ...s connection option KAW DN mm A in B mm L mm 8 Rd 28 1 8 10 426 15 Rd 28 1 8 10 462 3A version available order code for Additional approval option LP in combination with Ra 0 8 m order code for Measur...

Страница 64: ...roove C D A B E X X L 1 5 0 06 2 0 0 08 A0015627 37 Detail X Asymmetrical process connection the part shown in gray is provided by the supplier Engineering unit mm in DIN 11864 2 Form A flange with gr...

Страница 65: ...13 22 6 471 15 FB 37 13 22 6 610 25 FB 37 13 22 6 744 40 50 65 35 6 737 40 FB 50 65 35 6 859 50 64 16 48 6 856 50 FB 64 1 48 6 1268 80 91 19 72 9 1268 3A version available order code for Additional ap...

Страница 66: ...onnections in US units Flange connections ASME B16 5 C D A B E L 1 5 0 06 2 0 0 08 3 5 0 14 DN 125 5 DN 100 4 A0015621 40 Engineering unit mm in Flange according to ASME B16 5 Cl 150 1 4301 304 wetted...

Страница 67: ...4 92 3 50 4 0 75 0 87 1 01 27 56 1 6 10 4 50 4 0 88 1 02 1 61 27 87 1 FB 6 10 4 50 4 0 88 0 94 1 4 32 24 2 6 50 5 00 8 0 75 1 1 2 07 32 56 2FB 6 50 5 00 8 0 75 1 69 2 16 47 64 3 8 27 6 63 8 0 88 1 65...

Страница 68: ...87 33 46 2 FB 1 2 3 05 2 37 49 92 3 3 3 58 2 87 49 92 3A version available order code for Additional approval option LP in combination with Ra 32 in Ra 16 in order code for Measuring tube material opt...

Страница 69: ...centric Tri Clamp Titanium DN in Order code for Process connection option Clamp in A in B in L in FEA 0 98 0 37 16 81 FEC 0 98 0 62 18 23 FB FEE 1 1 99 0 87 23 74 1 FEE 1 1 99 0 87 23 74 1FB FEG 1 1 9...

Страница 70: ...40 1 6 0 89 16 81 Rd 40 1 6 0 89 18 23 1 Rd 40 1 6 0 89 23 74 1FB Rd 40 1 6 0 89 28 98 1 Rd 60 1 6 1 4 29 06 1 FB Rd 60 1 6 1 4 33 74 2 Rd 70 1 6 1 91 33 78 2FB Rd 70 1 6 1 91 49 53 3 Rd 98 1 6 2 83...

Страница 71: ...90 65 3 57 158 6 22 15FB FB NPT 90 65 3 57 158 6 22 25 1 NPT 90 65 3 57 296 11 66 25FB 1FB NPT 90 65 3 57 296 11 66 40 1 NPT 103 35 4 07 392 15 44 40FB 1 FB NPT 103 35 4 07 392 15 44 50 2 NPT 117 75...

Страница 72: ...ode for Housing option A Compact aluminum coated Aluminum AlSi10Mg coated Order code for Housing option B Compact hygienic stainless Hygienic version stainless steel 1 4301 304 Order code for Housing...

Страница 73: ...er for cable entry with internal thread G Adapter for cable entry with internal thread NPT Device plug Electrical connection Material Plug M12x1 Socket Stainless steel 1 4404 316L Contact housing Poly...

Страница 74: ...the plug in memory HistoROM DAT which contains the process and measuring device data and the event logbook No need to reconfigure For devices with Modbus RS485 the data recovery function is implement...

Страница 75: ...following device version Order code for Output option N EtherNet IP 5 3 1 2 4 A0016961 1 Ethernet network 2 Automation system e g RSLogix Rockwell Automation 3 Workstation for measuring device operat...

Страница 76: ...ncy switch output Order code for Output option L PROFIBUS DP Order code for Output option N EtherNet IP HART 1 2 3 A0016926 46 Connection for the order code for Output option B 4 20 mA HART pulse freq...

Страница 77: ...ernet connecting cable with RJ45 plug EtherNet IP 1 2 3 A0016940 48 Connection for order code for Output option N EtherNet IP 1 Service interface CDI RJ45 and EtherNet IP interface of the measuring de...

Страница 78: ...The measuring device is certified for use in hazardous areas and the relevant safety instructions are provided in the separate Safety Instructions XA document Reference is made to this document on the...

Страница 79: ...licitly stated in the order For devices with nominal diameters less than or equal to DN 25 1 this is neither possible nor necessary With the PED G1 x x category marking on the sensor nameplate Endress...

Страница 80: ...cation packages are available to enhance the functionality of the device Such packages might be needed to address safety aspects or specific application requirements The application packages can be or...

Страница 81: ...ume flow temperature and density The following viscosity measurements are performed on liquids Dynamic viscosity Kinematic viscosity Temperature compensated viscosity kinematic and dynamic in relation...

Страница 82: ...nd sizing Endress Hauser measuring devices Calculation of all the necessary data for identifying the optimum flowmeter e g nominal diameter pressure loss accuracy or process connections Graphic illust...

Страница 83: ...llowing The CD ROM provided for the device depending on the device version the CD ROM might not be part of the delivery The W M Device Viewer Enter the serial number from the nameplate www endress com...

Страница 84: ...of the HART Communication Foundation Austin USA PROFIBUS Registered trademark of the PROFIBUS User Organization Karlsruhe Germany Modbus Registered trademark of SCHNEIDER AUTOMATION INC EtherNet IPTM...

Отзывы: