10 Technical data
Proline Promass 83 FOUNDATION Fieldbus
100
Hauser
Suitability for CIP cleaning
yes
Suitability for SIP cleaning
yes
Electromagnetic compatibility
(EMC)
To EN 61326/A1 and NAMUR recommendation NE 21
10.1.9
Operating conditions: Process
Medium temperature range
Sensor:
• Promass F, A, H: –50...+200 °C
• Promass F:
−
50...+350 °C (high-temperature version)
• Promass M, I: –50...+150 °C
• Promass E: –50...+125 °C
Seals:
• Promass F, E, H, I: no internal seals
• Promass M: Viton –15...200 °C; EPDM –40...+160 °C; silicon –60...+200 °C;
Kalrez –20...+275 °C; FEP-jacketed (not for gas applications): –60...+200 °C
• Promass A (only for mounting sets with threaded connections):
Viton –15...200 °C; EPDM –40...+160 °C; silicon –60...+200 °C; Kalrez –20...+275 °C
Limiting medium pressure
range (rated pressure)
The material load curves (pressure-temperature diagrams) for the process connections are to be
found in the following documents:
• Technical Information Promass 80/83 F, M (TI 053D/06/en)
• Technical Information Promass 80/83 E (TI 061D/06/en)
• Technical Information Promass 80/83 A (TI 054D/06/en)
• Technical Information Promass 80/83 H, I (TI 052D/06/en)
Pressure ranges of secondary containment:
• Promass F: DN 8...50: 40 bar or 600 psi; DN 80: 25 bar or 375 psi;
DN 100...150: 16 bar or 250 psi; DN 250: 10 bar or 150 psi
• Promass M: 100 bar or 1500 psi
• Promass E: No secondary containment
• Promass A: 25 bar or 375 psi
• Promass H: DN 8...15: 25 bar or 375 psi; DN 25...50: 16 bar or 250 psi
• Promass I: 40 bar or 600 psi
Limiting flow
See Page 91 ff. (“Measuring range”)
Select nominal diameter by optimising between required flow range and permissible pressure loss.
See Page 91 for a list of max. possible full scale values.
• The minimum recommended full scale value is approx.
1
/
20
of the max. full scale value.
• In most applications, 20...50% of the maximum full scale value can be considered ideal.
• Select a lower full scale value for abrasive substances such as fluids with entrained solids (flow
velocity < 1 m/s).
• For gas measurement the following rules apply:
– Flow velocity in the measuring tubes should not be more than half the sonic velocity
(0.5 Mach).
– The maximum mass flow depends on the density of the gas (see formula on Page 93)
Содержание Proline Promass 83
Страница 24: ...3 Installation Proline Promass 83 FOUNDATION Fieldbus 24 Endress Hauser ...
Страница 34: ...4 Wiring Proline Promass 83 FOUNDATION Fieldbus 34 Endress Hauser ...
Страница 64: ...6 Commissioning Proline Promass 83 FOUNDATION Fieldbus 64 Endress Hauser ...
Страница 66: ...7 Maintenance Proline Promass 83 FOUNDATION Fieldbus 66 Endress Hauser ...
Страница 90: ...9 Trouble shooting Proline Promass 83 FOUNDATION Fieldbus 90 Endress Hauser ...
Страница 116: ...Index Proline Promass 83 FOUNDATION Fieldbus 116 Endress Hauser ...
Страница 118: ...www endress com worldwide BA065D 06 en 12 04 50098623 FM SGML 6 0 ...