Commissioning
Proline Promag W 400 HART
112
Hauser
Parameter
Prerequisite
Description
Selection / User
entry
Factory setting
Value current output 1
In the
Current output
simulation
parameter, the
On
option is selected.
Enter the current value for
simulation.
3.59 to 22.5 mA
3.59 mA
Frequency output simulation 1 to n
In the
Operating mode
parameter, the
Frequency
option is selected.
Switch the simulation of the
frequency output on and off.
• Off
• On
Off
Frequency value 1 to n
In the
Frequency output
simulation 1 to n
parameter,
the
On
option is selected.
Enter the frequency value for
the simulation.
0.0 to 12
500.0 Hz
0.0 Hz
Pulse output simulation 1 to n
In the
Operating mode
parameter, the
Pulse
option is
selected.
Set and switch off the pulse
output simulation.
For
Fixed value
option:
Pulse width
parameter
(→ 90) defines the
pulse width of the pulses
output.
• Off
• Fixed value
• Down-counting
value
Off
Pulse value 1 to n
In the
Pulse output
simulation 1 to n
parameter,
the
Down-counting value
option is selected.
Enter the number of pulses for
simulation.
0 to 65
535
0
Switch output simulation 1 to n
In the
Operating mode
parameter, the
Switch
option
is selected.
Switch the simulation of the
switch output on and off.
• Off
• On
Off
Switch status 1 to n
–
Select the status of the status
output for the simulation.
• Open
• Closed
Open
Device alarm simulation
–
Switch the device alarm on and
off.
• Off
• On
Off
Diagnostic event category
–
Select a diagnostic event
category.
• Sensor
• Electronics
• Configuration
• Process
Process
Diagnostic event simulation
–
Select a diagnostic event to
simulate this event.
• Off
• Diagnostic event
picklist (depends
on the category
selected)
Off
*
Visibility depends on order options or device settings
10.7 Protecting settings from unauthorized access
The following options exist for protecting the configuration of the measuring device from
unintentional modification after commissioning:
• Write protection via access code for the local display and Web browser
• Write protection via write protection switch
• Write protection via keypad lock → 67
10.7.1 Write protection via access code
The effects of the user-specific access code are as follows:
• Via local operation, the parameters for the measuring device configuration are write-
protected and their values can no longer be changed.
• Device access is protected via the Web browser, as are the parameters for the measuring
device configuration.