Technical data
Proline Promag L 400 HART
130
Hauser
Influence of ambient
temperature
o.r. = of reading; o.f.s. = of full scale value
Current output
Temperature coefficient
Typically
±
50 ppm/
°
C o.r. or
±
1 µA/
°
C
Pulse/frequency output
Temperature coefficient
Max.
±
50 ppm/
°
C
16.7
Installation
16.8
Environment
Ambient temperature range
Storage temperature
The storage temperature corresponds to the operating temperature range of the measuring
transmitter and the appropriate measuring sensors.
• Protect the measuring device against direct sunlight during storage in order to avoid unacceptably
high surface temperatures.
• Select a storage location where moisture cannot collect in the measuring device as fungus or
bacteria infestation can damage the liner.
• If protection caps or protective covers are mounted these should never be removed before installing
the measuring device.
Degree of protection
Transmitter
• As standard: IP66/67, type 4X enclosure
• When housing is open: IP20, type 1 enclosure
Sensor
• As standard: IP66/67, type 4X enclosure
• Optionally available for remote version:
IP68, type 6P enclosure (for DN
£
300 (12") only possible in conjunction with stainless steel
flanges)
Not suitable for use in corrosive atmospheres/liquids or in buried applications if special precautions
are not taken.
Shock resistance
Acceleration up to 2 g following IEC 600 68-2-6
Vibration resistance
Acceleration up to 2 g following IEC 600 68-2-6
Mechanical load
• Protect the transmitter housing against mechanical effects, such as shock or impact; the use of the
remote version is sometimes preferable.
• Never use the transmitter housing as a ladder or climbing aid.
Electromagnetic compatibility
(EMC)
• As per IEC/EN 61326 and NAMUR Recommendation 21 (NE 21)
• Complies with emission limits for industry as per EN 55011 (Class A)