Device functions Proline Promag 55 FOUNDATION Fieldbus
3 Transducer Block
Hauser
83
Low Flow Cut Off -
Assign
AUTO - OOS
Use this parameter to assign the switch point for the low flow cut off.
Options:
OFF
VOLUME FLOW
MASS FLOW
Factory setting:
VOLUME FLOW
Low Flow Cut Off -
On Value
AUTO - OOS
Use this function to specify the switch-on point for low flow cut off. Low
flow cut off is active if the value entered is not equal to 0.
User input:
5-digit floating-point number [unit]
Factory setting:
Nominal diameter and country dependent
!
Note!
• When the low flow cut off is triggered, a flow value of "0" is output via
the output value OUT (AI Block). In addition, the status changes to
UNCERTAIN.
• Choice of unit: see "Low Flow Cut Off - Unit" parameter
Low Flow Cut Off -
Unit
read only
Use this parameter to view the unit for the low flow cut off.
!
Note!
The unit for low flow cut off is determined by means of the "System Unit -
Volume Flow" or "System Unit - Mass Flow" parameter (
Low Flow Cut Off -
Off Value
AUTO - OOS
Use this function to enter the switch-off (
b
) point for low flow cut off.
Enter the switch-off point as a positive hysteresis (
H
) from the switch-on
point (
a
).
User input:
Integer 0 to 100%
Factory setting:
50%
A0003882
m
= switch-on point,
n
= switch-off point
a
Low flow cut off is switched on
b
Low flow cut off is switched off (a + a
⋅
H)
H
Hysteresis value: 0 to 100%
■
Low flow cut off active
Q
Flow
"Flow" Transducer Block/base index 1400
Parameter
Write access with
operating mode
(MODE_BLK)
Description
t
H
Q
m
n
b
a
Содержание Proline Promag 55
Страница 60: ...8 Block SUPERVISION Device Functions Proline Promag 55 FOUNDATION Fieldbus 60 Endress Hauser ...
Страница 66: ...10 Index local operation Device Functions Proline Promag 55 FOUNDATION Fieldbus 66 Endress Hauser ...
Страница 68: ...Table of contens FOUNDATION Fieldbus Device Functions Proline Promag 55 FOUNDATION Fieldbus 68 Endress Hauser ...
Страница 129: ...Device Functions Proline Promag 55 FOUNDATION Fieldbus Endress Hauser 129 ...
Страница 130: ...www endress com worldwide BA127D 06 en 09 06 71032705 FM SGML 6 0 ...