Proline Promag 55 FOUNDATION Fieldbus
Commissioning
Hauser
65
Configuration of the "Analog Input function blocks"
The measuring device has five Analog Input function blocks that can be assigned to the various
process variables. The following description provides an example for the Analog Input function
block 1 (base index: 500).
14. Enter the desired name for the Analog Input function block (optional).
Factory setting: ANALOG_INPUT_1xxxxxxxxxxx
15. Open the Analog Input function block 1.
16. Set the operating mode in the MODE_BLK parameter group (TARGET parameter) to OOS, i.e.
block Out Of Service.
17. Using the CHANNEL parameter select the process variable that is to be used as the input value
for the function block algorithm (scaling and limit value monitoring functions). The following
settings are possible:
18. In the XD_SCALE parameter group, select the desired engineering unit and the block input
range (e.g. measurement range of the flow application) for the process variable in question (see
the example below).
"
Caution!
Make sure that the selected unit is suitable for the measurement variable of the selected
process variable. Otherwise, the BLOCK_ERROR parameter will display the error message
"Block Configuration Error", and the block operating mode cannot be set to AUTO.
Process variable
Channel parameter
Calculated mass flow
1
Volume flow
2
Totalizer 1
7
Totalizer 2
8
Totalizer 3
9
Conductivity
10
The following process variables are available if the add-on software "Solids
content flow" is installed on the device (order option)
Target mass flow
40
% Target mass
41
Target volume flow
42
% Target volume
43
Carrier mass flow
45
% Carrier mass flow
46
Carrier volume flow
47
% Carrier volume flow
48
The following process variables are available if the add-on software "Advanced
Diagnositcs" is installed on the device (order option).
Deviation coating electrode 1
120
Deviation coating electrode 2
121
Deviation electrode potential 1
122
Deviation electrode potential 2
123
Deviation volume flow
124
Deviation noise value
125
Содержание Proline Promag 55
Страница 2: ......
Страница 120: ...www endress com worldwide BA126D 06 EN 07 09 71089883 FM SGML6 0 ProMoDo ...