SmarTec S CLD 132 PROFIBUS-PA/-DP
Operation
26
EHauser
Configuration examples with Simatic HW-Konfig
Ê
SmarTec S CLD 132 full configuration using the manufacturer-specific
GSD file
With this configuration, all data blocks supported by the transmitter are activated.
Byte
length
(Input)
Byte
length
(Output)
Data blocks
Status
Access
GSD
Block description
GSD
Extended
block code
0 ... 4
–
Analog Input
block 1
(Main meas.
value)
active
read
Main Process Value
0x42, 0x84, 0x08,
0x05
5 ... 9
–
Analog Input
Block 2
(Temp.)
active
read
Temperature
0x42, 0x84, 0x08,
0x05
0 ... 1
MRS
(Measuring
Range
Switch)
active
write
MRS
0x82, 0,81, 0x05,
0x05