Operating menu
Tankside Monitor NRF81
236
Hauser
"Administration" submenu
Navigation
Setup → Advanced setup → Administration
Define access code
Navigation
Setup → Advanced setup → Administration → Define access code
Description
Define release code for write access to parameters.
User entry
0 to 9
999
Factory setting
0
Additional information
Read access
Operator
Write access
Maintenance
If the factory setting is not changed or 0 is defined as the access code, the parameters
are not write-protected and the configuration data of the device can then always be
modified. The user is logged on in the
Maintenance
role.
The write protection affects all parameters marked with the symbol in this
document.
Once the access code has been defined, write-protected parameters can only be
modified if the access code is entered in the
Enter access code
parameter.
Device reset
Navigation
Setup → Advanced setup → Administration → Device reset
Description
Reset the device configuration - either entirely or in part - to a defined state.
Selection
• Cancel
• To fieldbus defaults
• To factory defaults
• Restart device
Factory setting
Cancel
Additional information
Read access
Operator
Write access
Maintenance
**
Visibility depends on communication