Micropilot NMR81
Diagnostyka i usuwanie usterek
Hauser
101
Numer
diagnostyczny
Krótki tekst
Działanie naprawcze
Sygnał
statusu
[z fabryki]
Reakcje
diagnostyczne
[z fabryki]
844
Process value out of
specification
1. Check process value
2. Check application
3. Check sensor
S
Warning
844
Process value out of
specification
S
Warning
903
Current loop 1 … 2
1. Check device
configuration.
2. Check wiring.
F
Alarm
904
Digital output 1 … 8
1. Check device
configuration.
2. Check wiring.
F
Alarm
941
Echo lost
1. Check process value
2. Check application
3. Check sensor
S
Warning
942
In safety distance
1. Check level
2. Check safety distance
3. Reset self holding
S
Warning
943
In blocking distance
Reduced accuracy
Check level
S
Warning
950
Advanced diagnostics
Maintain your diagnostic
event
M
Warning
961
Alarm 1 … 4 HighHigh
1. Check level
2. Check configuration
settings
C
Warning
962
Alarm 1 … 4 High
1. Check level
2. Check configuration
settings
C
Warning
963
Alarm 1 … 4 Low
1. Check level
2. Check configuration
settings
C
Warning
964
Alarm 1 … 4 LowLow
1. Check level
2. Check configuration
settings
C
Warning
965
Alarm 1 … 4 HighHigh
1. Check level
2. Check configuration
settings
F
Alarm
966
Alarm 1 … 4 High
1. Check level
2. Check configuration
settings
F
Alarm
967
Alarm 1 … 4 Low
1. Check level
2. Check configuration
settings
F
Alarm
968
Alarm 1 … 4 LowLow
1. Check level
2. Check configuration
settings
F
Alarm
970
Overtension
1. Check displacer and
process conditions
2. Release overtension
C
Alarm
971
Undertension
Check displacer and process.
C
Alarm
1)
Diagnostyka zachowania może zostać zmieniona.