Micropilot FMR62B HART

Installation

Hauser

13

Flange size

Number of screws

Tightening torque

JIS

10K 50A

4

40 to 60 Nm

Information about the mounting nozzle

The maximum nozzle length 

H

max

 depends on the nozzle diameter 

D

.

The maximum length of the nozzle H

max

 depends on the nozzle diameter D

D

H

max

H

øD

max

50 to 80 mm (2 to 3.2 in)

600 mm (24 in)

80 to 100 mm (3.2 to 4 in)

1

 

000 mm (40 in)

100 to 150 mm (4 to 6 in)

1

 

250 mm (50 in)

≥ 150 mm (6 in)

1

 

850 mm (74 in)

In the case of longer nozzles, reduced measuring performance must be expected.
Please note the following:

• The end of the nozzle must be smooth and free from burrs.

• The edge of the nozzle should be rounded.

• Mapping must be performed.

• Please contact the manufacturer's support department for applications with nozzles

that are higher than indicated in the table.

10.3.4   Antenna, PTFE cladded, flush mount 80 mm (3 in)

The cladding on the antenna also acts as a process seal. An additional seal is not

required for installation.

Mounting cladded flanges

Note the following for cladded flanges:

• Use the same number of flange screws as the number of flange bores provided.

• Tighten the screws with the necessary torque (see Table).

• Retighten after 24 hours or after the first temperature cycle.

• Depending on the process pressure and temperature, check and retighten the screws,

where necessary, at regular intervals.

The PTFE flange cladding normally acts simultaneously as a seal between the nozzle and

the device flange.

Flange size

Number of screws

Tightening torque

EN

DN80 PN10/16

8

40 to 55 Nm

Содержание Micropilot FMR62B

Страница 1: ...are not a substitute for the Operating Instructions pertaining to the device Detailed information is provided in the Operating Instructions and other documentation Available for all device versions vi...

Страница 2: ...Micropilot FMR62B HART 2 Endress Hauser Order code Ext ord cd Ser no www endress com deviceviewer Endress Hauser Operations App XXXXXXXXXXXX XXXXX XXXXXX XXX XXXX XX Serial number 1 3 2 A0023555...

Страница 3: ...1 10 4 Post mounting check 17 11 Electrical connection 17 11 1 Connecting requirements 17 11 2 Connecting the device 19 11 3 Ensuring the degree of protection 25 11 4 Post connection check 25 12 Opera...

Страница 4: ...ry NOTICE This symbol contains information on procedures and other facts which do not result in personal injury 1 2 Symbols for certain types of information and graphics Permitted Procedures processes...

Страница 5: ...observed the measuring device may be used for the following measurements only Measured process variables level distance signal strength Calculable process variables volume or mass in any shape of vess...

Страница 6: ...l related area e g explosion protection pressure equipment safety Check the nameplate to verify if the device ordered can be put to its intended use in the approval related area Observe the specificat...

Страница 7: ...evice features on the delivery note Device Viewer www endress com deviceviewer manually enter the serial number from the nameplate All the information about the measuring device is displayed Endress H...

Страница 8: ...kaging or by the process connection Always secure lifting equipment slings eyes etc at the process connection and never lift the device by the electronic housing or sensor Pay attention to the center...

Страница 9: ...Hauser 9 10 2 Mounting requirements 10 2 1 Internal vessel fittings A0031777 Avoid internal fittings point level switches temperature sensors struts vacuum rings heating coils baffles etc inside the...

Страница 10: ...it is perpendicular to the product surface The maximum reach of the antenna can be reduced or additional interference signals can occur if the antenna is not installed perpendicular to the product 10...

Страница 11: ...es reduced measuring performance must be expected Please note the following The end of the nozzle must be smooth and free from burrs The edge of the nozzle should be rounded Mapping must be performed...

Страница 12: ...in the table 10 3 3 Antenna PTFE cladded flush mount 50 mm 2 in The cladding on the antenna also acts as a process seal An additional seal is not required for installation Mounting cladded flanges No...

Страница 13: ...g must be performed Please contact the manufacturer s support department for applications with nozzles that are higher than indicated in the table 10 3 4 Antenna PTFE cladded flush mount 80 mm 3 in Th...

Страница 14: ...o 105 Nm ASME NPS 3 Cl 150 4 65 to 95 Nm NPS 3 Cl 300 8 40 to 55 Nm NPS 4 Cl 150 8 45 to 65 Nm NPS 4 Cl 300 8 55 to 80 Nm NPS 6 Cl 150 8 85 to 125 Nm NPS 6 Cl 300 12 60 to 85 Nm NPS 8 Cl 150 8 115 to...

Страница 15: ...nozzle should be rounded Mapping must be performed Please contact the manufacturer s support department for applications with nozzles that are higher than indicated in the table 10 3 5 Turning the ho...

Страница 16: ...h off the supply voltage before opening the measuring device 2 1 4 0 7 Nm 3 4 A0038224 1 If fitted release the screw of the cover lock for the electronics compartment cover using the Allen key 2 Unscr...

Страница 17: ...securing screws and cover lock tightened securely Does the measuring device comply with the measuring point specifications For example Process temperature Process pressure Ambient temperature Measurin...

Страница 18: ...evice is connected 1 1 1 B C D 1 A A0046583 A Single compartment housing plastic B Single compartment housing aluminum C Dual compartment housing D Dual compartment housing L form 1 Ground terminal fo...

Страница 19: ...11 2 1 Supply voltage The supply voltage depends on the selected type of device approval Non hazardous Ex d Ex e 10 5 to 35 VDC Ex i 10 5 to 30 VDC Nominal current 4 to 20 mA The power unit must be te...

Страница 20: ...e is always necessary in the case of a low impedance power supply Take the voltage drop into consideration Maximum 6 V for a 250 communication resistor 11 2 4 Overvoltage protection The overvoltage pr...

Страница 21: ...be connected to the outer ground terminal of the device before the power supply lines are connected A suitable circuit breaker should be provided for the device in accordance with IEC EN 61010 The ca...

Страница 22: ...62B HART 22 Endress Hauser 11 2 6 Terminal assignment Single compartment housing 1 2 3 A0042594 3 Connection terminals and ground terminal in the connection compartment 1 Positive terminal 2 Negative...

Страница 23: ...T Electrical connection Endress Hauser 23 Dual compartment housing 1 2 3 A0042803 4 Connection terminals and ground terminal in the connection compartment 1 Positive terminal 2 Negative terminal 3 Int...

Страница 24: ...and ground terminal in the connection compartment 1 Positive terminal 2 Negative terminal 3 Internal ground terminal 11 2 7 Cable entries 1 1 1 1 2 A B C D 2 2 2 A0046584 A Single compartment housing...

Страница 25: ...uded with the delivery along with the corresponding documentation Thread NPT1 2 IP66 68 TYPE 4X 6P Dummy plug transport protection IP22 TYPE 2 HAN7D plug 90 degrees IP65 NEMA Type 4X M12 plug When hou...

Страница 26: ...tches on the HART electronic insert Display on off 1 2 on off 3 4 A0046129 6 Operating keys and DIP switches on the HART electronic insert 1 Operating key for reset password for Bluetooth login and Ma...

Страница 27: ...s access code protects the device configuration from unauthorized access If an incorrect access code is entered the user obtains the access rights of the Operator role 12 4 Access to the operating men...

Страница 28: ...sly takes the user back up a level in the menu Press and hold the keys simultaneously to return to the upper level 12 4 2 Operation via Bluetooth wireless technology optional Requirement Device with d...

Страница 29: ...password changed by the user is also saved in the Bluetooth display 12 5 Access to the operating menu via the operating tool Access via the operating tool is possible Via HART communication e g Commu...

Страница 30: ...guration parameters Guidance menu Commissioning wizard 13 1 Preliminaries The measuring range and the unit in which the measured value is transmitted correspond to the data on the nameplate LWARNING T...

Страница 31: ...Connection for Commubox FXA195 and AMS TrexTM device communicator 4 AMS TrexTM device communicator 5 Computer with operating tool e g DeviceCare FieldCare AMS Device View SIMATIC PDM 6 Commubox FXA19...

Страница 32: ...display first needs to be unlocked 1 Press the key for at least 2 s A dialog box appears 2 Unlock the display operation 3 Select the Language parameter in the main menu 4 Press the key 5 Select the de...

Страница 33: ...ssioning with the Commissioning wizard In FieldCare DeviceCare SmartBlue and on the display the Commissioning wizard is available to guide the user through the initial commissioning steps Complete thi...

Страница 34: ......

Страница 35: ......

Страница 36: ...www addresses endress com 71575925 71575925...

Отзывы: