Field Communication with 
Liquisys M CXM 223 / 253

Operating Instructions

Содержание Liquisys M CXM 223

Страница 1: ...A 208C 07 en 07 02 51501609 Supplement to BA 193C 07 en BA 194C 07 en BA 199C 07 en BA 200C 07 en BA 214C 07 en BA 246C 07 en HART Field Communication with Liquisys M CXM 223 253 Operating Instruction...

Страница 2: ...Liquisys M CXM 223 253 HART 2 Endress Hauser...

Страница 3: ...nnection 8 4 1 Quick connection guide 8 4 2 Connecting the HART handheld terminal DXR 275 9 4 3 Connecting a PC with operating programme 9 4 4 Post connection check 10 5 Operation 11 5 1 Display and o...

Страница 4: ...DC voltage A terminal at which DC voltage is applied or through which DC flows AC voltage A terminal at which sine form AC voltage is applied or through which AC flows Ground connection A grounded ter...

Страница 5: ...onnel The technical personnel must be authorised for the specified activities by the system operator Technical personnel must have read and understood theses Operating Instructions and must adhere to...

Страница 6: ...version acc to the nameplate s chap 2 1 1 Accessories s chap 9 Standard Operating Instructions BA 193C 07 en CLM BA 194C 07 en CPM BA 199C 07 en COM BA 200C 07 en CUM BA 214C 07 en CCM BA 246C 07 en C...

Страница 7: ...2 System architecture Liquisys M CXM 223 253 HART 3 2 Post installation check After installing the transmitter carry out the following checks Instrument status and specifications Note Is the transmitt...

Страница 8: ...owing connection options at their disposal Direct connection to the transmitter by means of current output 1 terminals 31 32 Connection by means of the 4 20 mA circuit Note The measuring circuit s min...

Страница 9: ...nsmitter 2 power supply 3 screening 4 other switching units or PLC with passive input 5 HART handheld terminal DXR 275 4 3 Connecting a PC with operating programme You require a HART modem Commubox FX...

Страница 10: ...red specifications Use genuine E H cables for sensor connection see Accessories chapter in the standard Operating Instructions Are the mounted cables strain relieved Is the cable type route completely...

Страница 11: ...he key assignment and the other icons 5 2 Operation via the HART handheld terminal DXR 275 The HART handheld terminal DXR 275 is operated by means of push buttons with which the instrument functions o...

Страница 12: ...ons are determined by V0 A to indicate the vertical position and by H0 9 to indicate the horizontal position Fig 9 Operation of Liquisys M CLM 223 253 via the operating programme Commuwin II Note Refe...

Страница 13: ...mV V1H7 V1H7 V1H7 Measured value display uncomp V0H7 Measured value display in FNU V0H7 Measured value display in nA V0H8 Error display V8H0 V8H0 V8H0 V8H0 V8H0 Editing mode V8H9 V8H9 V8H9 V8H9 V8H9 A...

Страница 14: ...3 V2H2 V2H2 V2H2 V2H2 V2H2 O3x1 V2H3 V2H3 V2H3 V2H3 V2H3 O3x2 V2H4 V2H4 V2H4 V2H4 V2H4 O3x3 V2H5 V2H5 V2H5 V2H5 V2H5 O334 V2H6 V2H6 V2H6 V2H6 V2H6 O335 V2H7 V2H7 V2H7 V2H7 V2H7 O336 V2H8 V2H8 V2H8 V2H...

Страница 15: ...R Relays R1 V3H0 V3H0 V3H0 V3H0 V3H0 R2 V3H1 V3H1 V3H1 V3H1 V3H1 R2x1 V3H2 V3H2 V3H2 V3H2 V3H2 R2x2 V4H0 V4H0 V4H0 V4H0 V4H0 R2x3 V4H1 V4H1 V4H1 V4H1 V4H1 R2x4 V4H2 V4H2 V4H2 V4H2 V4H2 R2x5 V4H3 V4H3...

Страница 16: ...V5H4 V5H4 K6 V5H5 V5H5 K7 V5H6 V5H6 K8 V5H7 V5H7 K9 V5H8 S Service S1 S2 V9H0 VAH5 V9H0 V9H0 V9H0 S3 S4 V9H1 VAH6 V9H1 V9H1 V9H1 S5 V9H2 VAH7 V9H2 V9H2 V9H2 S6 V9H3 V9H7 V9H3 V9H3 V9H3 S7 S8 VAH3 VAH...

Страница 17: ...2 VAH2 VAH2 VAH2 VAH2 I Interface I1 VAH1 VAH1 VAH1 VAH1 VAH1 I2 VAH0 VAH0 VAH0 VAH0 VAH0 C Calibration C134 V1H6 ind V Offset V1 V0H8 V0H8 V2 V0H9 V0H9 Field coding Function group VH position CPM 2X3...

Страница 18: ...ing functionalities are linked to them Recognising HART devices Reading off digital measured values pH value conductivity temperature etc Common practice commands Common practice commands offer functi...

Страница 19: ...vice information Byte 9 11 device identification 1 Read main measured value Access type Read none Byte 0 HART unit ID of the main measured value Byte 1 4 main measured value 2 Read the main measured v...

Страница 20: ...nd date Access type Read none Byte 0 5 tag Byte 6 17 tag description Byte 18 20 date Note You can write the tag tag description and date using command 18 14 Read sensor information on the main measure...

Страница 21: ...write 0 s 35 Write measuring range of main measured value Access type Write Write the desired measuring range Byte 0 HART unit ID for the main measured value Byte 1 4 end of measuring range value for...

Страница 22: ...can be controlled by the byte transmitted Byte 0 Burst control byte 0 Off 1 On Byte 0 Burst control byte Device specific commands 142 Read display format Access type Read Reads the number of places b...

Страница 23: ...ts V Byte 1 2 HART unit ID Byte 3 4 VH variable 155 Write VH matrix variable with 2 byte unit Access code Write Writes the Commuwin II variables with this command Byte 0 VH Position lower 4 bits H upp...

Страница 24: ...ld lead to damage to instruments 6 2 Setting the device address All HART devices have the device address 0 on leaving the factory This address can be changed to connect up several devices for HART com...

Страница 25: ...Liquisys M CXM 223 253 HART 7 Maintenance Endress Hauser 25 7 Maintenance Note Please refer to the standard Operating Instructions for information on maintenance of the measuring point...

Страница 26: ...0 Error temperature sensor 5 E030 Error SCS reference electrode 6 E032 Error electrode slope 7 E033 Error zeropoint 2 0 E034 Error Offset range redox 1 E041 Error calibration parameter 2 E042 Error di...

Страница 27: ...7 Transmitter error 3 E008 Sensor error 4 E010 Error temperature sensor 5 E025 Airset value exceeded 6 E036 Cell constant exceeded 7 E037 Cell constant undershot 2 0 E045 Calibration aborted 1 E046 no...

Страница 28: ...or sensor slope 4 E044 Error signal stability 5 E057 Measuring range main parameter exceeded 6 E058 Measuring range temperature undershot 7 E059 Measuring range temperature exceeded 2 0 E063 Current o...

Страница 29: ...er error 3 E008 Sensor error 4 E010 Error temperature sensor 5 E025 not used 6 E026 Wiper error 7 E032 Error sensor slope 2 0 E036 not used 1 E037 not used 2 E044 Error stability criteria 3 E045 Calib...

Страница 30: ...l 5 E033 Error zeropoint 6 E034 Error offset range redox 7 E035 Error offset range sensor 963 2 0 E042 Error distance calibration value buffer 2 to zeropoint 1 E043 Error distance calibration value bu...

Страница 31: ...m threshold limit contact 1 exceeded 1 E068 Alarm threshold limit contact 2 exceeded 2 E069 Alarm threshold limit contact 3 exceeded 3 E070 Alarm threshold limit contact 4 exceeded 4 E080 Current outp...

Страница 32: ...mpatible device via a 4 20 mA line Order No DXR 275 Commubox FXA 191 HART modem Commubox FXA 191 Interface module between HART interface and series PC interface Technical Information TI 237F 00 en Ord...

Страница 33: ...n II Current range 4 20 mA Load 250 500 Power supply with passive current output 24 V DC Power supply 100 115 230 V AC 24 V AC DC Frequency 48 62 Hz Power consumption max 7 5 VA On site operation Via...

Страница 34: ...r messages 26 F Function 24 Function check 24 H HART commands 18 19 Common practice commands 21 Device specific commands 22 Universal commands 19 HART handheld terminal DXR 275 11 32 HART modem Commub...