Liquiphant FTL62 HART
Diagnostics and troubleshooting
Hauser
43
11.4 Adapting the diagnostic information
The event level can be configured:
Navigation: Diagnostics → Diagnostic settings → Configuration
11.5 Queued diagnostic messages
The display alternates between the queued diagnostic messages and the measured value.
Queued diagnostic messages can also be displayed in the
Active diagnostics
parameter.
Navigation: Diagnostics → Active diagnostics
11.6 Diagnostic list
All the diagnostic messages that are currently queued can be displayed in the
Diagnostic
list
submenu.
Navigation: Diagnostics → Diagnostic list
Diagnostic
number
Short text
Remedy instructions
Status
signal
[from the
factory]
Diagnostic
behavior
[from the
factory]
Diagnostic of sensor
004
Sensor defective
1. Restart device
2. Replace electronics
3. Replace device
F
Alarm
007
Sensor defective
1. Check fork
2. Replace device
F
Alarm
042
Sensor corroded
1. Check fork
2. Replace device
F
Alarm
049
Sensor corroded
1. Check fork
2. Replace device
M
Warning
061
Sensor electronics faulty
Replace electronics
F
Alarm
062
Sensor connection faulty
1. Check Main to sensor
connection
2. Replace electronics
F
Alarm
081
Sensor initialization faulty 1. Restart device
2. Contact service
F
Alarm
Diagnostic of electronic
201
Electronics faulty
1. Restart device
2. Replace electronics
F
Alarm
203
HART Device Malfunction Check device specific diagnosis.
S
Warning
204
HART Electronic Defect
Check device specific diagnosis.
F
Alarm
242
Firmware incompatible
1. Check software
2. Flash or change main
electronic module
F
Alarm
252
Module incompatible
1. Check if correct electronic
module is plugged
2. Replace electronic module
F
Alarm
263
Electronic incompatible
Check electronic module type
F
Alarm
270
Main electronics defective Replace main electronics
F
Alarm
272
Main electronics faulty
1. Restart device
2. Contact service
F
Alarm