Liquiphant FTL31
Mounting
Hauser
11
5
Mounting
5.1
Mounting requirements
5.1.1
Orientation
Installation is possible in any position in a vessel, pipe or tank.
1
2
3
A0036961
2
Installation examples
1
Overfill prevention or upper level detection (maximum safety)
2
Dry running protection for pump (minimum safety)
3
Lower level detection (minimum safety)
5.1.2
Switch point
The switch point
A
on the sensor depends on the orientation of the point level switch (water
+25 °C (+77 °F), 1 bar (14.5 psi).
A
~30 (1.2)
A
A
~10.5(0.4)
~
13 (0.5)
A0020734
3
Orientation: vertical from above, vertical from below, horizontal; dimensions in mm (in)
5.1.3
Viscosity
Switching delays may occur in the case of highly viscous liquids. Make sure that the liquid can
easily run off the tuning fork: