Levelflex M FMP 40 with Foundation Fieldbus
6 Commissioning
Hauser
63
Function "empty calibr." (005)
This function is used to enter the distance from the flange (reference point of the
measurement) to the minimum level (=zero).
Function "full calibr." (006)
This function is used to enter the distance from the minimum level to the maximum level
(=span).
⇒
0%
E
E = empty calibration (= zero)
Emax = probe length – lower blocking distance
⇒
100%
0%
F
F = full calibration (= span)
Fmax = E – upper blocking distance