Electrical connection
Levelflex FMP56, FMP57 FOUNDATION Fieldbus
48
Hauser
7.1.4
Power supply
PROFIBUS PA, FOUNDATION Fieldbus
"Power supply; Output"
"Approval"
Terminal voltage
E:
2-wire; FOUNDATION Fieldbus, switch output
G:
2-wire; PROFIBUS PA, switch output
• Non-Ex
• Ex nA
• Ex nA[ia]
• Ex ic
• Ex ic[ia]
• Ex d[ia] / XP
• Ex ta / DIP
• CSA GP
9 to 32 V
• Ex ia / IS
• Ex ia + Ex d[ia] / IS + XP
9 to 30 V
1)
Feature 020 of the product structure
2)
Feature 010 of the product structure
3)
Input voltages up to 35 V will not spoil the device.
Polarity sensitive
No
FISCO/FNICO compliant
according to IEC 60079-27
Yes
7.1.5
Overvoltage protection
If the measuring device is used for level measurement in flammable liquids which requires
the use of overvoltage protection according to DIN EN 60079-14, standard for
test procedures 60060-1 (10 kA, pulse 8/20 μs), overvoltage protection has to be ensured
by an integrated or external overvoltage protection module.
Integrated overvoltage protection
An integrated overvoltage protection module is available for 2-wire HART as well as
PROFIBUS PA and FOUNDATION Fieldbus devices.
Product structure: Feature 610 "Accessory mounted", option NA "Overvoltage protection".
Technical data
Resistance per channel
2 × 0.5 Ω max.
Threshold DC voltage
400 to 700 V
Threshold impulse voltage
< 800 V
Capacitance at 1 MHz
< 1.5 pF
Nominal arrest impulse voltage (8/20 μs)
10 kA
External overvoltage protection
HAW562 or HAW569 from Hauser are suited as external overvoltage protection.
For detailed information please refer to the following documents:
• HAW562: TI01012K
• HAW569: TI01013K
Содержание Levelflex FMP56
Страница 210: ...www addresses endress com 71344087 71344087 ...