Operating menu
Levelflex FMP56, FMP57 FOUNDATION Fieldbus
144
Hauser
17.3.2 "Analog input 1 to 5" submenu
There is an
Analog inputs
submenu for every AI block of the device. The AI block is used
to configure the measured value transmission to the bus.
Only the most basic properties of the AI block can be configured in this submenu. For
a detailed configuration of the AI blocks refer to the
Expert
menu.
Navigation
Setup → Analog inputs → Analog input 1 to 5
Block tag
Navigation
Setup → Analog inputs → Analog input 1 to 7 → Block tag
Description
Defined to be unique throughout the control system at one plant site. The tag may be
changed using the FB_Tag service.
Factory setting
Channel
Navigation
Setup → Analog inputs → Analog input 1 to 7 → Channel
Description
Use this function to select the input value that should be processed in the analog input
function block.
Selection
• Uninitialized
• Level linearized
• Absolute echo amplitude
• Absolute EOP amplitude
• Absolute interface amplitude
• Distance
• Electronic temperature
• EOP shift
• Interface linearized
• Interface distance
• Measured capacitance
• Relative echo amplitude
• Relative interface amplitude
• Noise of signal
• Terminal voltage
• Thickness upper layer
• Calculated DC value
• Analog output adv. diagnostics 2
• Analog output adv. diagnostics 1
Factory setting
Uninitialized
*
Visibility depends on order options or device settings