Mounting
Levelflex FMP53 FOUNDATION Fieldbus
8
Hauser
5
Mounting
5.1
Mounting requirements
5.1.1
Suitable mounting position
A
1
2
C
B
3
A0014130
1
Installation conditions for Levelflex
Spacing requirements when mounting
• Distance (A) between the vessel wall and rod probes:
• For smooth metallic walls: > 50 mm (2 in)
• For plastic walls: > 300 mm (12 in) to metallic parts outside the vessel
• Distance (B) between rod probes and internal fittings (4): > 300 mm (12 in)
• When using more than one Levelflex:
Minimum distance between the sensor axes: 100 mm (3.94 in)
• Distance (C) from the end of the probe to the bottom of the vessel: > 10 mm (0.4 in)
Содержание Levelflex FMP53 FOUNDATION Fieldbus
Страница 23: ......
Страница 24: ...www addresses endress com 71565960 71565960...