Levelflex FMP55 HART
Operating menu
Hauser
187
Description of parameters
Navigation
Expert → Diagnostics → Simulation
Assign measurement variable
Navigation
Expert → Diagnostics → Simulation → Assign meas.var.
Description
Selct process variable to be simulated.
Selection
• Off
• Level
• Interface
• Thickness upper layer
• Level linearized
• Interface linearized
• Thickness linearized
Factory setting
Off
Additional information
• The value of the variable to be simulated is defined in the
Process variable value
• If
Assign measurement variable
≠
Off
, a simulation is active. This is indicated by a
diagnotic message of the
Function check (C)
category.
Process variable value
Navigation
Expert → Diagnostics → Simulation → Proc. var. value
Prerequisite
Assign measurement variable (→ 187)
Off
Description
Specify value of the process value being simulated.
User entry
Signed floating-point number
Factory setting
0
Additional information
Downstream measured value processing and the signal output use this simulation value. In
this way, users can verify whether the measuring device has been configured correctly.
*
Visibility depends on order options or device settings