
Operating menu
Levelflex FMP55 HART
120
Hauser
Mapping end point
Navigation
Setup → Map. end point
Prerequisite
Manual map
or
Distance too small
Description
Specify new end of the mapping.
User entry
0 to 200
000.0 m
Factory setting
0.1 m
Additional information
This parameter defines up to which distance the new mapping is to be recorded. The
distance is measured from the reference point, i.e. from the lower edge of the mounting
flange or the threaded connection.
For reference purposes the
Present mapping
parameter (→ 119) is displayed
together with this parameter. It indicates up to which distance a mapping has already
been recorded.
Record map
Navigation
Setup → Record map
Prerequisite
Manual map
or
Distance too small
Description
Start recording of the map.
Selection
• No
• Record map
• Delete map
Factory setting
No
Additional information
Meaning of the options
•
No
The map is not recorded.
•
Record map
The map is recorded. After the recording is completed, the new measured distance and
the new mapping range appear on the display. When operating via the local display,
these values must be confirmed by pressing .
•
Delete map
The mapping (if one exists) is deleted and the device displays the recalculated measured
distance and the mapping range. When operating via the local display, these values must
be confirmed by pressing .
Содержание Levelflex FMP52
Страница 20: ...Storage Transport Levelflex FMP55 HART 20 Endress Hauser 1 2 4 3 A0015471...
Страница 197: ......
Страница 198: ...www addresses endress com 71344071 71344071...