Operating menu
Levelflex FMP55 HART
118
Hauser
Interface distance
Navigation
Setup → Interface dist.
Prerequisite
Operating mode (→ 111)
Interface
or
Interface with capacitance
Description
Displays the measured distance D
I
between the reference point (lower edge of flange or
threaded connection) and the interface.
Additional information
D
I
D
I
A0013202
The unit is defined in the
Distance unit
Confirm distance
Navigation
Setup → Confirm distance
Description
Specify, whether the measured distance matches the real distance.
Depending on the selection the device automatically sets the range of mapping.
Selection
• Manual map
• Distance ok
• Distance unknown
• Distance too small
• Distance too big
• Tank empty
• Delete map
Factory setting
Distance unknown
*
Visibility depends on order options or device settings