Installation
TMT180
8
Hauser
3.2
Installation
3.2.1
Typical European installation
For installation, proceed as follows:
Installing in a sensor connection head to DIN 43 729 Form B (see Fig. 3)
• Feed the sensor inset cables (Pos. 5) through the central hole in the head transmitter (Pos. 4).
• Place the installation springs (Pos. 3) onto the screws (Pos. 2).
• Feed the installation screws (Pos. 2) through the holes in the head transmitter and the holes in
the sensor inset (Pos. 5). Fix both screws using the E-rings (Pos. 6).
• Position the head transmitter in the connection head in such a way that the current output
terminals (terminal 1 and 2) are towards the cable entry gland (Pos. 7).
• Fix the head transmitter (Pos. 4) and sensor inset (Pos. 5) into the connection head.
Installation in a field housing (see Fig. 4)
• Feed the installation screws (Pos. 2) with installation springs (Pos. 3) through the holes in the
head transmitter (Pos. 4). Fix these using the E-rings (Pos. 5).
• Screw the head transmitter into the field housing using a screwdriver.
"
Caution!
In order to avoid damaging the head transmitter, do not over-tighten the installation screws.
Fig. 3:
Installation of head transmitter into a Form B
sensor connection head.
Fig. 4:
Installation of head transmitter into field
housing.