41
Hauser
HART Loop Converter HMX50
Activating Password Protection
To protect parameterization from unauthorized changes, you can enable password
protection. Information about password protection see chapter 3.4.2.
1. Use the
▴
or
▾
buttons to select the desired setting.
2. To enable password protection, select On Password.
3. Confirm your selection with OK.
4. To disable password protection, select Off Password.
5. Confirm your selection with OK.
Resetting the Device to Factory Settings
1. Use the
▴
or
▾
buttons to select On Reset.
On Reset flashes.
2. Confirm your selection with OK.
The device is reset to factory settings. All entries you have defined in parameterization
mode will be lost.
Displaying the Software Version
Use the
▴
or
▾
buttons to display the version.
The software version of the device software is displayed.
4 Operation
4.1 Indicators during Operation
The isolated barrier displays the following operating modes and fault messages during
operation.
BA00371FEN_1417.fm Page 41 Tuesday, August 15, 2017 4:08 PM