5.4.5
Device status / Error messages
You can read the extended device status, in this case, current error messages, via Command
"48". The command delivers information which are partly coded in bits (see table below).
!
Note!
Explanation of the device status and error messages and their elimination ® Page 84 ff.
HART 5
Byte-bit
Error No.
0-0
001
Serious device error
0-1
011
Measuring amplifier has faulty EEPROM
0-2
012
Error when accessing data of the measuring amplifier EEPROM
1-1
031
S-DAT: Defective or missing
1-2
032
S-DAT: Error accessing saved values
1-3
041
T-DAT: Defective or missing
1-4
042
T-DAT: Error accessing saved values
1-5
051
I/O board and the amplifier board are not compatible.
3-3
111
Totalizer checksum error
3-4
121
I/O board and the amplifier board (software versions) are not compatible.
3-6
205
T-DAT: Data download not successful
3-7
206
T-DAT: Data upload not successful
4-3
251
Internal communication fault on the amplifier board.
4-4
261
No data reception between amplifier and I/O board
5-7
339
Flow buffer:
The temporarily buffered flow portions (measuring mode for pulsating
flow) could not be cleared or output within 60 seconds.
6-0
340
6-1
341
6-2
342
6-3
343
Frequency buffer:
The temporarily buffered flow portions (measuring mode for pulsating
flow) could not be cleared or output within 60 seconds.
6-4
344
6-5
345
6-6
346
6-7
347
Pulse buffer:
The temporarily buffered flow portions (measuring mode for pulsating
flow) could not be cleared or output within 60 seconds.
7-0
348
7-1
349
7-2
350
7-3
351
Current output:
The actual value for the flow lies outside the set limits.
7-4
352
7-5
353
7-6
354
7-7
355
Frequency output:
The actual value for the flow lies outside the set limits.
8-0
356
8-1
357
8-2
358