Installation
Proline Promag P 500 HART
24
Hauser
For heavy sensors DN ≥ 350 (14")
A0016276
Orientation
The direction of the arrow on the sensor nameplate helps you to install the sensor
according to the flow direction (direction of medium flow through the piping).
Orientation
Recommendation
A
Vertical orientation
A0015591
B
Horizontal orientation, transmitter at
top
A0015589
C
Horizontal orientation, transmitter at
bottom
A0015590
D
Horizontal orientation, transmitter at
side
A0015592
1)
Applications with low process temperatures may decrease the ambient temperature. To maintain the
minimum ambient temperature for the transmitter, this orientation is recommended.
2)
Applications with high process temperatures may increase the ambient temperature. To maintain the
maximum ambient temperature for the transmitter, this orientation is recommended.
3)
To prevent the electronics module from overheating in the case of a sharp rise in temperature (e.g. CIP- or
SIP processes), install the device with the transmitter component pointing downwards.
Horizontal
• Ideally, the measuring electrode plane should be horizontal. This prevents brief
insulation of the two measuring electrodes by entrained air bubbles.
• Empty pipe detection only works if the transmitter housing is pointing upwards as
otherwise there is no guarantee that the empty pipe detection function will actually
respond to a partially filled or empty measuring tube.