Electrical connection
Micropilot FMR60B HART
22
Hauser
6
Electrical connection
6.1
Connecting requirements
6.1.1
Cover with securing screw
In the case of devices for use in the hazardous area with a certain type of protection, the
cover is sealed by a securing screw.
NOTICE
If the securing screw is not positioned correctly, the cover cannot provide secure
sealing.
‣
Open the cover: slacken the screw of the cover lock with a maximum of 2 turns so that
the screw does not fall out. Fit the cover and check the cover seal.
‣
Close the cover: screw the cover securely onto the housing, making sure that the
securing screw is positioned correctly. There should not be any gap between the cover
and housing.
2 x
0.7 Nm
4
A0039520
2
Cover with securing screw
6.1.2
Potential equalization
The protective ground on the device must not be connected. If necessary, the potential
matching line can be connected to the outer ground terminal of the transmitter before the
device is connected.
1
1
1
B
C
D
1
A
A0046583
A
Single compartment housing, plastic
B
Single compartment housing, aluminum
C
Dual compartment housing
D
Dual compartment housing, L-form
1
Ground terminal for connecting the potential matching line
L
WARNING
Explosion Hazard!
‣
Please refer to the separate documentation on applications in hazardous areas for the
safety instructions.
For optimum electromagnetic compatibility:
• Keep the potential matching line as short as possible
• Observe a cross-section of at least 2.5 mm
2
(14 AWG)