Operation options

Micropilot FMR53, FMR54 FOUNDATION Fieldbus

28

Hauser

Channel

Measured value

32949

Level linearized

33044

Relative echo amplitude

7.6  

Methods

The FOUNDATION Fieldbus Specification allows for the use of methods to simplify device

operation. A method is a sequence of interactive steps to be carried out in the specified order

so as to configure certain device functions.
The following methods are available for the devices:

Restart

This method is located in the resource block and is used to configure the 

Reset device

parameter. This resets the device parameters to a specific state.

ENP Restart

This method is located in the resource block and allows the parameters of the electronic

nameplate (

E

lectronic 

N

ame 

P

late) to be changed.

Setup

This method is located in the SETUP transducer block and is used for basic configuration of

the measurement parameters (measurement units, tank or vessel type, medium, empty and

full calibration).

Linearization

This method is located in the ADV_SETUP transducer block and allows the linearization

table to be managed for the purpose of converting the level measured into a volume, a mass

or a flow rate.

Self Check

This method is located in the EXPERT_CONFIG transducer block and is used to perform a

device self-test.

8  

Operation options

The device can be operated as follows:

• Operation via operating menu (display)

• DeviceCare / FieldCare, see Operating Instructions

• SmartBlue (app), Bluetooth (optional), see Operating Instructions

  A0033202

 11

Download link

Содержание FOUNDATION Fieldbus Micropilot FMR53

Страница 1: ...ions they are not a substitute for the Operating Instructions pertaining to the device Detailed information about the device can be found in the Operating Instructions and the other documentation Avai...

Страница 2: ...ord cd Ser no www endress com deviceviewer Endress Hauser Operations App XXXXXXXXXXXX XXXXX XXXXXX XXX XXXX XX Serial number 1 3 2 A0023555 2 About this document 2 1 Symbols used 2 1 1 Safety symbols...

Страница 3: ...inals that must be connected to ground prior to establishing any other connections The ground terminals are located on the inside and outside of the device Interior ground terminal protective earth is...

Страница 4: ...vice described in these Operating Instructions is intended for continuous non contact level measurement in liquids pastes and sludges Due to its operating frequency of approx 6 GHz a maximum radiated...

Страница 5: ...and with the device Wear the required personal protective equipment as per national regulations 3 4 Operational safety Risk of injury Operate the device only if it is in proper technical condition fre...

Страница 6: ...ry note and the product sticker identical Are the goods undamaged Does the data on the nameplate match the order specifications on the delivery note Is the DVD with the operating tool present If requi...

Страница 7: ...e from wall to nozzle outer edge 1 6 of the vessel diameter However the device must not under any circumstances be mounted closer than 15 cm 5 91 in to the tank wall 1 Use of a weather protection cove...

Страница 8: ...2 Orientation 5 3 Internal vessel fittings A0018944 Avoid the location of internal fittings limit switches temperature sensors struts vacuum rings heating coils baffles etc inside the signal beam Take...

Страница 9: ...e of the maximum energy density 3dB width Microwaves are also emitted outside the signal beam and can be reflected off interfering installations a D W a D _ 2 2 tan W A0016891 1 Relationship between b...

Страница 10: ...3 66 m 12 ft 3 01 m 9 9 ft 2 37 m 7 8 ft 12 m 39 ft 4 88 m 16 ft 4 02 m 13 ft 3 16 m 10 ft 15 m 49 ft 6 1 m 20 ft 5 02 m 16 ft 3 95 m 13 ft 20 m 66 ft 8 14 m 27 ft 6 69 m 22 ft 5 27 m 17 ft 5 6 Free s...

Страница 11: ...Micropilot FMR53 FMR54 FOUNDATION Fieldbus Mounting Endress Hauser 11 A B 90 90 90 90 90 90 90 90 90 90 A0018974 Depending on the device version the marking may be a circle or two parallel lines...

Страница 12: ...mm 3 94 in 250 mm 9 84 in The inactive part 1 of the rod antenna must project out of the nozzle For flanges with PTFE cladding Observe the instructions for mounting cladded flanges The PTFE flange cla...

Страница 13: ...simultaneously as a seal between the nozzle and the device flange Flange size Number of screws Tightening torque EN DN50 PN10 16 4 45 to 65 Nm DN50 PN25 40 4 45 to 65 Nm DN80 PN10 16 8 40 to 55 Nm DN8...

Страница 14: ...ween the flange holes to aid the alignment This marking must be aligned towards the tank wall as much as possible A B 90 90 90 90 90 90 90 90 90 90 A0018974 Depending on the device version the marking...

Страница 15: ...through plastic walls Dielectric constant of the medium r 10 Use an antenna 250 mm 10 in if possible The distance from the tip of the antenna to the tank should be approx 100 mm 4 in If possible avoi...

Страница 16: ...ermal radiation or convection The insulation should not be higher than the neck of the device 1 5 8 Turning the transmitter housing To provide easier access to the connection compartment or display mo...

Страница 17: ...counterclockwise 2 Unscrew the electronics compartment cover and check the cover seal replace it if necessary 5 9 2 Turning the display module 1 2 A0036401 1 Pull out the display module with a gentle...

Страница 18: ...ent 1 2 2 5 Nm 3 mm A0021451 1 Screw down the cover of the electronics compartment 2 Turn the securing clamp 90 in the clockwise direction and using an Allen key 3 mm tighten the screw of the securing...

Страница 19: ...3 and 4 without integrated overvoltage protection 3 Connection switch output open collector terminals 3 and 4 with integrated overvoltage protection 4 Connection PROFIBUS PA FOUNDATION Fieldbus termin...

Страница 20: ...output 1 Approval 2 Terminal voltage E 2 wire FOUNDATION Fieldbus switch output G 2 wire PROFIBUS PA switch output Non Ex Ex nA Ex nA ia Ex ic Ex ic ia Ex d ia XP Ex ta DIP CSA GP 9 to 32 V 3 Ex ia I...

Страница 21: ...ce Connect the potential matching line to the outer ground terminal before applying the power supply Required tools accessories For devices with a cover lock Allen key AF3 Wire stripper When using str...

Страница 22: ...f using shielded cables Connect the cable shield to the ground terminal 6 2 3 Plug in spring force terminals The electrical connection of device versions without an integrated overvoltage protection i...

Страница 23: ...F configuration program The Cff file Common File Format cff The device description DD is in one of the following formats Device description format 4 sym ffo Device description format 5 sy5 ff5 Data fo...

Страница 24: ...he device for the measuring task and for the FF system 7 3 Device identification and addressing FOUNDATION Fieldbus identifies the device using its identification code device ID and automatically assi...

Страница 25: ...ATA_TRANSFER_ TRDHROM xxxxxxxxxxx ANALOG_INPUT_1_ AI xxxxxxxxxxx ANALOG_INPUT_2_ UNK xxxxxxxxxxx DISCRETE_INPUT_ DI xxxxxxxxxxx MULTIPLE_AO_ MAO xxxxxxxxxxx ARITHMETIC_ AR xxxxxxxxxxx INPUT_SELECTOR_...

Страница 26: ...e discrete output block MDO 1 PID block PID 1 arithmetic block AR 1 signal characterizer block SC 1 input selector block ISEL 1 integrator block IT 1 analog alarm block AAL In addition to the pre inst...

Страница 27: ..._CONFIG SETUP SERVICE_SENSOR PV SV ESC OPEN OPEN E Device_01 F mm 4841 000 A0017217 10 Block configuration when device is delivered S Sensor PV Primary value level linearized SV Secondary value distan...

Страница 28: ...source block and allows the parameters of the electronic nameplate Electronic Name Plate to be changed Setup This method is located in the SETUP transducer block and is used for basic configuration of...

Страница 29: ...ag and error symbol if an error is active 1 2 Measured value symbols 1 3 Measured value 1 4 Unit 2 Measured value display bar graph 1 value 2 1 Bar graph for measured value 1 2 2 Measured value 1 incl...

Страница 30: ...4 13 Display module 1 Operating keys Key assignment Key Navigate down in the picklist Edit the numerical values or characters within a function Key Navigate up in the picklist Edit the numerical value...

Страница 31: ...ghter setting key and key press and hold keys simultaneously Increases the contrast darker setting 9 2 Opening the context menu Using the context menu the user can call up the following menus quickly...

Страница 32: ...pecial measuring conditions For converting the measured value scaling linearization For scaling the output signal Diagnostics Contains the most important parameters for diagnosing the condition of the...

Страница 33: ...0 50 Operation Setup Main menu 0104 1 Display language English Espa ol Fran ais Display language English Deutsch 0104 1 Espa ol Fran ais Display language English Deutsch 0104 1 Betrieb Setup Hauptmen...

Страница 34: ...the respective bin type Note Workbench test deactivates all filters This option should exclusively be used for tests 4 Setup Medium group Specify media group aqueous DK 4 or other DK 1 9 5 Setup Empty...

Страница 35: ...nce Compare the distance displayed with the actual value to start recording an interference echo map 11 Setup Advanced setup Level Level unit Select the level unit m mm ft in factory setting The react...

Страница 36: ...www addresses endress com 71575726 71575726...

Отзывы: