Display FHX50
XA01053F-A
Hauser
13
Device type: FHX50
Basic specifications
Safety instructions:
General
• Staff must meet the following conditions for mounting, electrical installation, commissioning and
maintenance of the device:
– Be suitably qualified for their role and the tasks they perform
– Be trained in explosion protection
– Be familiar with national regulations (e.g. IEC/EN 60079-14)
• Install the device according to the manufacturer's instructions and national regulations (IEC/EN 60079-14).
• Do not operate the device outside the specified electrical, thermal and mechanical parameters.
• Modifications to the device can affect the explosion protection and must be carried out by staff authorized
to perform such work by Hauser.
Safety instructions:
Special conditions
Permitted ambient temperature range at the electronics housing: –40 °C
T
a
+80 °C.
Observe the information in the temperature tables.
• In the event of additional or alternative special varnishing on the housing or other metal parts:
– Observe the danger of electrostatic charging and discharge.
– Do not rub surfaces with a dry cloth.
Basic specification, Position 4 (Housing) = D
• Avoid electrostatic charging of the housing (e.g. friction, cleaning, maintenance, strong medium flow).
Position
Selected option
Description
1, 2
Approval
BA
BM
IA
IM
ATEX
II 1 G Ex ia IIC T6 Ga
ATEX
II 2 D Ex ia IIIC Txx°C Db
IECEx Ex ia IIC T6 Ga
IECEx Ex ia IIIC Txx°C Db
3
Display; Operation
A
C
E (in preparation)
None, use existing device display
SD02 4-line, push b data backup function
SD03 4-line, illum., touch c data backup function
4
Housing
B (in preparation)
D
Single compartment, 316L
Single compartment, plastics PBT
6
Option
Measurement Device
A
B
Prepared for remote display FHX50
Not prepared for display FHX50 + retrofit kit