Synchronizer FHG66
Technical data
Input
Cascading input
• For connection to a Synchronizer FHG66
• Galvanically isolated from additional power supply and output
• Connecting cable: twin-core; shielding not required (except in the event of strong electromagnetic
interference)
• Cable requirements:
• Max. capacitance: 120 nF
• Max. resistance: 1
000 Ω
• Max. inductance: 0.65 mH
• Cable: not shielded/not twisted
• Signal transmission: closed current loop 0 to 5 mA, max. 12 V
Output
Alarm relay
•
Type:
Potential-free change-over contact
•
Switching delay:
0 to 3 s
•
Switching capacity (DC voltage):
• U: maximum 40 V
• I: maximum 2 A
• P: maximum 80 W
•
Switching capacity (AC voltage):
• U: maximum 250 V
• I: maximum 2 A
• P: maximum 500 VA at cos phi ≥ 0.7
•
Operating life:
Min. 10
5
switching cycles with maximum contact load
•
Function indicator:
Light emitting diodes for operation, faults and error assignment; device
detects and reports errors in the configuration and in the connected devices
•
Overvoltage category:
II
•
Protection class:
2 (double/reinforced isolation)
Signal on alarm
• Fault indicated by red LED
• Fault assignment by yellow LEDs
• Alarm relay deenergized
Power supply
• Supply voltage: 18 to 35 VDC (power supply with safe isolation required)
• Power consumption: max.1 W
• Overvoltage category: II
• Protection class: 2
• Pollution degree: 2