Commissioning
Dosimag
34
Hauser
10.4.3 Configuring the pulse/frequency/switch output
The
Pulse/frequency/switch output 1 to 2
submenu contains all the parameters that
must be configured for the configuration of the selected output type.
Configuring the pulse output
In the
Operating mode
parameter (→ 34), one of the two options can be selected for
the pulse output:
•
Pulse
option: Quantity-proportional pulse with pulse width to be configured.
•
Automatic pulse
option: Quantity-proportional pulse with on/off ratio of 1:1
Navigation
"Setup" menu → Pulse/frequency/switch output 1 to 2
Structure of submenu for pulse output
‣
Pulse/frequency/switch output 1
to 2
Operating mode
Channel 2
Assign pulse output
Value per pulse
Pulse width
Failure mode
Invert output signal
Parameter overview with brief description
Parameter
Prerequsite
Description
Selection / User
entry
Factory setting
Operating mode
–
Define the output as a pulse,
frequency or switch output.
• Off
• Pulse
• Automatic pulse
• Frequency
• Switch
•
Pulse/frequency/
switch output 1
submenu:
Pulse
option
•
Pulse/frequency/
switch output 1 to
2
submenu:
Switch
option
Channel 2
The
Pulse
option is selected in
the
Operating mode
parameter.
Select impulse with or without
time offset.
• Off
• Redundant 0°
• Redundant 90°
• Redundant 180°
Off
Assign pulse output
One of the following options is
selected in the
Operating
mode
parameter:
• Pulse
• Automatic pulse
Select process variable for
pulse output.
• Off
• Volume flow
Off