Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
Description of parameters
Hauser
61
EMPTY CALIB. (010)
Entry
Enter level, volume, mass or percentage value for the lower calibration point (container
empty).
The values entered for the EMPTY CALIB. and EMPTY PRESSURE parameters form the
pressure-level value pair for the lower calibration point. The unit is selected via the
OUTPUT UNIT parameter (
Page 60).
Prerequisite:
• CALIBRATION MODE = Dry
Factory setting:
0.0
EMPTY PRESSURE (011)
Entry
Enter pressure value for the lower calibration point (container empty).
See also EMPTY CALIB.
Prerequisite:
• CALIBRATION MODE = Dry
Factory setting:
0.0
FULL CALIB. (004)
Entry
Enter height, volume, mass or percentage value for the upper calibration point (container
full).
The values entered for the FULL CALIB. and FULL PRESSURE parameters form the
pressure-level value pair for the upper calibration point. The unit is selected via the
OUTPUT UNIT parameter (
Page 60).
Prerequisite:
• CALIBRATION MODE = Dry
Factory setting:
100.0
FULL PRESSURE (005)
Entry
Enter pressure value for the upper calibration point (container full).
See also FULL CALIB.
Prerequisite:
• CALIBRATION MODE = Dry
Factory setting:
100.0
SET LRV (013)
Entry
Enter value for the lower current value (4 mA). The unit is selected via the OUTPUT
UNIT parameter (
Factory setting:
0.0
SET URV (012)
Entry
Enter value for the upper current value (20 mA). The unit is selected via the OUTPUT
UNIT parameter (
Factory setting:
100.0
DAMPING VALUE (247)
Entry
Enter damping time (time constant
).
The damping affects the speed at which all subsequent elements, such as the on-site
display, measured value and current output react to a change in the pressure.
Input range:
0.0 to 999.0 s
Factory setting:
2.0 s or as per order specifications
Table 8: (GROUP SELECTION
) OPERATING MENU
SETTINGS
BASIC SETUP "Level",
LEVEL SELECTION "Level Easy Pressure"