Description of parameters
Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
104
Hauser
P01-xxxxxxxx-19-xx-xx-xx-099
Fig. 39:
LINEARISATION function group for digital communication
EDITOR TABLE
LINE-NUMB.
LIN. EDIT MODE
Editor Table
Measuring Table
Level measuring
mode only
EDITOR TABLE
LINE-NUMB.
X-VAL
Y-VAL
ACTIV LIN. TAB. X
ACTIV LIN. TAB. Y
TANK DESCRIPTION
TANK CONTENT MIN
TANK CONTENT MAX
TABLE SELECTION
QUICK SETUP
DISPLAY
SETTINGS
POSITION ADJUSTMENT
OPERATING MENU
Measured value
LINEARIZATION
Table 19: (GROUP SELECTION
) OPERATING MENU
SETTINGS
LINEARISATION – Digital
communication
Parameter name
Description
Prerequisite
:
• MEASURING MODE = Level (
see also Page 45).
• LEVEL MODE = Pressure Linearized or Height Linearized (
see also Page 68).
Note:
– See also Page 14 ff, Section 5 "Level measurement".
TANK CONTENT MIN
Entry
Enter the minimum tank contents to be expected.
The input limits for the calibration (editing limits) are derived from the value entered. The
closer the value entered corresponds to the minimum tank content to be expected, the
more accurate the measurement result.
!
Note!
• If you enter a new value for TANK CONTENT MIN, the value for SET LRV is also
changed. Use SET LRV to assign a %-value, volume value or mass value to the lower
current value. If you want to assign the lower current value a value other than that for
TANK CONTENT MIN, you must enter the desired value for SET LRV. (
SET LRV,
Page 98).
• For the setting LEVEL MODE "Height Linearized" and ASSIGN CURRENT "Linear",
the TANK CONTENT MIN parameter does not affect the SET LRV parameter. (
SET
LRV, Page 98 and ASSIGN CURRENT, Page 113)
Factory setting:
0.0