Description of parameters
Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
100
Hauser
P01-xxxxxxxx-19-xx-xx-xx-091
Fig. 38:
LINEARISATION function group for on-site operation
SET URV (638)
Entry
Depending on the setting in the LINEAR/SQROOT parameter (
Page 113), enter a flow
value or a pressure value for the upper current value (20 mA) here.
• LINEAR/SQROOT = Flow (square root) (factory setting)
flow value
• LINEAR/SQROOT = Differential pres.
pressure value
The following applies for the setting LINEAR/SQROOT "Flow (square root)":
• If you enter a new value for MAX. FLOW, the value for SET URV is also changed. If
you want to assign the upper current value a value other than that for MAX. FLOW,
you must enter the desired value for SET URV. (
MAX. FLOW, Page 95).
The following applies for the setting LINEAR/SQROOT "Differential pres.":
• If you enter a new value for MAX PRESS. FLOW, the SET URV value is also changed. If
you want to assign the upper current value a value other than that for MAX PRESS.
FLOW, you must enter the desired value for SET URV. (
MAX PRESS. FLOW,
Page 95).
Factory setting:
MAX. FLOW
Table 17: (GROUP SELECTION
) OPERATING MENU
SETTINGS
EXTENDED SETUP "Flow"
Parameter name
Description
1)
1)
EDITOR TABLE
EDITOR TABLE
MEASURING TABLE
Editor Table
Measuring Table
EDITOR TABLE
TANK CONTENT MIN
LIN. EDIT MODE
TANK DESCRIBTION
TANK CONTENT MAX
TABLE SELECTION
MEASURING TABLE
LANGUAGE
DISPLAY
SETTINGS
POSITION ADJUSTMENT
OPERATING MENU
GROUP SELECTION
Measured value
LINEARIZATION
Level measuring
mode only
1) Display via on-site display only
Table 18: (GROUP SELECTION
) OPERATING MENU
SETTINGS
LINEARISATION
– on-site operation
Parameter name
Description
Prerequisite
:
• MEASURING MODE = Level (
see also Page 45).
• LEVEL MODE = Pressure Linearized or Height Linearized (
see also Page 68).
Note:
– See also Page 14 ff, Section 5 "Level measurement".