Diagnostics and troubleshooting
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
108
Hauser
9.6
Response of outputs to errors
The device makes a distinction between the output behavior "Alarm", "Warning" and "Error".
See the following table and
93, Section 9.2 "Diagnostic information on local display".
Certain problems can be assigned the "GOOD" status via FF communication, see Section 9.4.1.
9.6.1
Analog Input Block
If the Analog Input Block receives an input or simulation value with the status BAD, the
Analog Input Block uses the failsafe mode defined in the FSAFE_TYPE
1
parameter.
The following options are available by means of the FSAFE_TYPE parameter:
• Last Good Value
The last valid value is used for further processing with the status UNCERTAIN.
• Fail SafeValue
733 Alarm/
Warning
S>Tmax ALARM
WINDOW
(TEMPERATURE_1_
USER_HIGH_LIMIT)
overshot
19
0
– Temperature measured value
has overshot the value
specified for the
TEMPERATURE_1_
USER_HIGH_LIMIT/Tmax
ALARM WINDOW
parameter.
– Check system/temperature
measured value.
– Change value for
TEMPERATURE_1_
USER_HIGH_LIMIT/Tmax
ALARM WINDOW if
necessary.
(
See also Operating
Instructions BA00303P,
parameter description or
these Operating Instructions)
56
Diagnostic
Code
Error
response
Message/description XD_
ERROR
Value Bit
BLOCK_
ERROR
Value Bit
Cause
Measure
Prio-
rity
Output
A (Alarm)
W (Warning)
E (Error: Alarm/Warning)
FOUNDATION
Fieldbus
The process variable in question is
transmitted with the status BAD.
Device continues measuring. The process
variable in question is transmitted with
the status UNCERTAIN.
For this error, you can enter whether the
device should react as in the event of an
alarm or as in the event of a warning.
See appropriate column for "Alarm" or
"Warning"
(
see Operating Instructions
BA00303P, parameter description),
REACTION_ON_ ALARM_NR/SELECT
ALARM TYPE parameter).
The GOOD status can also be assigned to
the individual error via the parameters
FF912_STATUS_SELECT_1 to
FF912_STATUS_SELECT _131.
Onsite display
– The measured value and message are
displayed alternately
– Measured value display:
-symbol is
permanently displayed.
Message display
– A + 3-digit number such as A122 and
– Description
– The measured value and message are
displayed alternately
– Measured value display:
-symbol
flashes.
Message display:
– W + 3-digit number such as W613
and
– Description
– The measured value and message are
displayed alternately
– Measured value display: see
corresponding "Alarm" or "Warning"
column
Message display:
– E + 3-digit number such as E731 and
– Description
Remote operation (FF
configuration
program/FieldCare)
In the event of an alarm, the ALARM
STATUS/ALARM_STATUS
1)
parameter
displays a 3-digit number such as 122
for "Sensor connection error, incorrect
data".
In the case of a warning, the ALARM
STATUS/ALARM_STATUS
parameter
displays a 3-digit number such as 613
for "Simulation is active".
In the case of an error, the ALARM
STATUS/ALARM_STATUS
parameter
displays a 3-digit number such as 731
for "Pmax ALARM WINDOW undershot".
1)
FF configuration program: Diagnostic Transducer Block. Menu path FieldCare: OPERATING MENU
MESSAGES