Deltabar S PROFIBUS PA
Commissioning
Hauser
37
7.5 Flow measurement
Before calibrating the Deltabar S, the impulse piping must be cleaned and filled with fluid.
7.5.1 Quick Setup menu for the Flow measurement – on-site display
See also Page 22, Section 4.2.3 "Function of the operating elements" and Page 23, 4.3 "On-site
operation via on-site display".
P01-xMD7xxxx-19-xx-xx-xx-076
Fig. 13: Quick Setup menu for Flow measuring mode
OP
E
RATING
ME
N
U
M
AX FLO
W
M
AX. PR
E
SS. FLO
W
POS.
ZE
RO A
D
J
U
ST
D
A
M
PING VAL
UE
Flow
Pressure
Level
ME
AS
U
R
ED
VAL
UE
Q
U
I
C
K S
E
T
U
P
GRO
U
P S
E
L
EC
TION
ME
AS
U
RING
M
O
DE
LANG
U
AG
E
On-site operation
Measured value display
On-site display: Switch from the measured value display to GROUP SELECTION with F.
GROUP SELECTION
Select MEASURING MODE.
MEASURING MODE
Select "Flow" option.
WARNING
!
Changing the measuring mode affects the span (URV)!
This situation can result in product overflow.
‣
If the measuring mode is changed, the span setting (URV) must be verified in the "Calibration"
"Basic Setup"
operating menu and, if necessary, reconfigured!
GROUP SELECTION
Select QUICK SETUP menu.
POS. ZERO ADJUST
Due to orientation of the device, there may be a shift in the measured value. You correct the MEASURED VALUE via the
POS. ZERO ADJUST parameter with the "Confirm" option, i. e. you assign the value 0.0 to the pressure present.
Содержание Deltabar S FMD 77
Страница 39: ...Deltabar S PROFIBUS PA Commissioning Endress Hauser 39...
Страница 40: ...www addresses endress com 71281260...