Operation options
Deltabar M PMD55 FOUNDATION Fieldbus
20
Hauser
7.2.3
Operating example: User-definable parameters
Example: Setting the "Set URV (014)" parameter from 100 mbar (1.5 psi) to
50 mbar (0.75 psi).
Menu path: Setup → Extended setup → Current output → Set URV
Set URV
014
Operation
The local display shows the parameter to be changed. The "mbar" unit is
defined in another parameter and cannot be changed here.
1
1 0 0 . 0 0 0
mbar
Press or to enter the edit mode.
The first digit is highlighted in black.
2
1
0 0 . 0 0 0
mbar
Use the key to change "1" to "5".
Press the key to confirm "5". The cursor jumps to the next position
(highlighted in black).
Confirm "0" with (second position).
3
5
0 0 . 0 0 0
mbar
The third digit is highlighted in black and can now be edited.
4
5 0
0
. 0 0 0
mbar
Use the key to change to the " " symbol.
Use to save the new value and exit the edit mode. See next graphic.
5
5 0
¿
. 0 0 0
mbar
The new value for the upper range value is 50 mbar (0.75 psi).
Use to exit the edit mode for the parameter.
Use or to return to the edit mode.
6
5 0 .
0 0 0
mbar
7.2.4
Operating example: Accepting the pressure present
Example: Setting position adjustment.
Menu path: Main menu → Setup → Position adjustment
Position adjustment
007 Operation
1 Cancel
The pressure for position adjustment is present at the device.
Confirm
2
Cancel
Use or to switch to the "Confirm" option. The active option is highlighted in
black.
Confirm
3
Adjustment has
been accepted!
Use the key to accept the applied pressure for position adjustment. The device
confirms the adjustment and goes back to the "Position adjustment" parameter.