Smart Transmitters
Configuration
For smart transmitters the Commulog is
simply connected into the 4...20 mA
analogue circuit.
•
A minimum load of 150
Ω
must always
be present on the line.
•
The maximum load is 650
Ω
.
For the Deltabar differential pressure
transmitter:
•
There is no need to pressurize during
configuration.
•
4
…
20 mA signals can be simulated
for the adjustment of instrumentation.
•
The differential pressure can be read
from matrix field V0H0 (Display 00).
Field Use
The Commulog VU 260 Z can also be
connected directly to the smart
transmitter:
•
A rugged, splash-proof housing
means it can be used outdoors.
•
It is suitable for use in explosion
hazardous areas Zone 1.
Smart Transmitters
The following are smart transmitters:
Deltabar PMD 130, FMD 130, 530, 533
Prosonic FMU 86...
Micropilot FMR 130.
150
Ω
Deltabar
Deltabar analogue
display
VU 260 Z
Power
supply
Other
instru-
ments
Alternative
VU 260 Z
connecton
Z
one 1
4
…
20 mA signal line
N
on-
E
x
Deltabar
Deltabar
Display
Other
instruments
VU 260 Z
Power
supply
150
Ω
4
…
20 mA signal line
Smart transmitters, e.g.
Deltabar can be
configured and
interrogated in the field
Connection diagram for
standard applications.
The Commulog
VU 260 Z can be
plugged into any part
of the circuit
Connection diagram for
explosion hazardous
area