Description of parameters
Cerabar S 4 to 20mA HART
22
Hauser
SET MAX. ALARM (342)
Entry
Enter current value for maximum alarm current.
See also OUTPUT FAIL MODE.
Input range:
21...23 mA
Factory setting:
22 mA
SET MIN. CURRENT (343)
Entry
Enter lower current limit.
Some switching units do not accept current values lower than 4.0 mA.
Options:
• 3.8 mA
• 4.0 mA
Factory setting:
3.8 mA