Cerabar M, Deltapilot M
Description of device parameters
Hauser
79
Description
Enter the output value for the lower calibration point (vessel empty). The unit defined in
"Output unit" must be used.
Note
• In the case of wet calibration, the level (e.g. vessel empty or partially filled) must actually
be available. The associated pressure is then automatically recorded by the device.
• In the case of dry calibration, the level (vessel empty) does not have to be available. For
the "In pressure" level selection, the associated pressure must be entered in the "Empty
pressure" parameter.
Factory setting
0.0
Empty pressure (29)
Write permission
Operators/Service engineers/Expert
Description
Enter the pressure value for the lower calibration point (vessel empty). See also "Empty
calib.".
Prerequisite
• "Level selection" = In pressure
• "Calibration mode" = Dry -> entry
• "Calibration mode" = Wet -> display
Factory setting
0.0
Full calib. (031)
Write permission
Operator/Maintenance/Expert
Description
Enter the output value for the upper calibration point (vessel full). The unit defined in
"Output unit" must be used.
Note
• In the case of wet calibration, the level (e.g. vessel full or partially filled) must actually be
available. The associated pressure is then automatically recorded by the device.
• In the case of dry calibration, the level (vessel full) does not have to be available. For the
"In pressure" level selection, the associated pressure must be entered in the "Full pressure"
parameter.
Factory setting
100.0
Full pressure (032)
Write permission
Operators/Service engineers/Expert
Description
Enter the pressure value for the upper calibration point (vessel full). See also "Full calib.".