Description of device parameters
Cerabar M, Deltapilot M
74
Hauser
Factory setting:
0
13.5 Expert → Measurement
Measuring mode (005)
Write permission
Operator/Maintenance/Expert
Description
Select the measuring mode.
The operating menu is structured differently depending on the measuring mode selected.
L
WARNING
Changing the measuring mode affects the span (URV)
This situation can result in product overflow.
‣
If the measuring mode is changed, the setting for the span (URV) must be checked in
the "Setup" operating menu and readjusted if necessary.
Selection
• Pressure
• Level
Factory setting
Pressure or according to order specifications
13.6 Expert → Measurement → Basic setup
Pos. zero adjust (007) (gauge pressure sensors))
Write permission
Operator/Maintenance/Expert
Description
Pos. zero adjustment – the pressure difference between zero (set point) and the measured
pressure need not be known.
Example
• Measured value = 2.2 mbar (0.033 psi)
• You correct the measured value via the "Pos. zero adjust" parameter with the "Confirm"
option. This means that you are assigning the value 0.0 to the pressure present.
• Measured value (after pos. zero adjustment) = 0.0 mbar
• The current value is also corrected.
Selection
• Confirm
• Cancel
Factory setting
Cancel
Calib. offset (008) (absolute pressure sensors)